Page 50
31-5000723 Rev. 0
Furnace Condensate
Drain Condensate
From Evaporator Coil
Optional
Overflow Switch
Field Provided Vent
1” min. 2” max. above
condensate drain.
Figure 41.
Condensate Trap With Optional Overflow
Switch
(1” min. to 2” Max.above
condensate drain connection)
Condensate
Drain Connection
Evaporator drain
line required
(Trap at coil is optional)
Field-Provided Vent
Figure 42. Furnace with Evaporator Coil Using a
Common Drain
(Unit shown in horizontal left−hand discharge position)
Condensate Drain
Connection
(4” min. to 5” Max. above
condensate drain connection)
5’ max.
PVC Pipe Only
Evaporator
Coil
Drain Pan
Piping from furnace and evaporator coil must slope down a minimum 1/4” per ft. toward trap
(Trap at coil is optional)
4”min
5”max
Field-Provided Vent
Figure 43. Furnace with Evaporator Coil Using a Common Drain