All the cables shall have got the European

authentication certificate.

5. The breaker of the air conditioner should

be  all-pole  switch;  and  the  distance

between its two contacts should be no less

3mm. Such means for disconnection must

be incorporation in the fixed wiring.

6. The  waste  battery  shall  be  disposed

properly.

7. The indoor unit installation height is at

least 2.5m.

    All electrical repairs must be carried out

by qualified electricians. Inadequate repairs

may result in a major source of danger for

the user of the air conditoiner.
    Do  not  damage  any  parts  of  the  air

conditioner  that  carry  refrigerant  by

piercing or perforating the air conditioner's

tubes with sharp or pointed items, crushing

or  twisting  any  tubes,  or  scraping  the

coatings off the surfaces. If the refrigerant

spurts out and gets into eyes, it may result

in serious eye injuries.
   Do not obstruct or cover the ventilation

grille of the air conditioner. Do not put

fingers  or  any  other  things  into  the

inlet/outlet and swing louver.
   Do not allow children to play with the air

conditioner. In no case should children be

allowed to sit on the outdoor unit.

Specifications

   The refrigerating circuit is leak-proof.

1. Applicable ambient temperature range:

The machine is adaptive in following

situation

Model

2. If the supply cord is damaged, it must be

replaced by the manufacturer or its service

agentor a similar qualified person.

Cautions

HBU-36HH03  HBU-42CH03
HBU-42CI03    HBU-42HI03
HBU-48CH03  HBU-48HJ03

HBU-48CK03

HBU-28CH03  HBU-28HH03

Power Cable

3. The wiring method should be in line with

the local wiring standard.

4. The power cable and connecting cable

are self-provided.

The requirement of the power cable:

The requirement of the connecting cable:

Model

Connecting cable

HBU-28CH03  HBU-36HH03
HBU-42CH03  HBU-42CI03

HBU-42HI03   HBU-48CH03
HBU-48HJ03   HBU-48CK03

3G  4.0mm

2

5G  2.5mm

2

HBU-28HH03

4G  0.75mm

2

6G  0.75mm

2

Cooling

Heating

Indoor

outdoor

DB 

WB 

Indoor

outdoor

Rated

27

19

35

24

20

14.5

7

6

Maximum

32

23

43

26

27

-

24

18

Minimum

18

14

10

6

15

-

-7

-

2

DB 

WB 

DB 

WB 

DB 

WB 

Summary of Contents for HBU-42CH03

Page 1: ...e air conditioner No 0150500604 C Operation Installation Manual HBU 28CH03 HBU 28HH03 HBU 36HH03 HBU 42CI03 HBU 42CH03 HBU 42HI03 HBU 48CH03 HBU 48HJ03 HBU 48CK03 CASSETTE TYPE AIR CONDITIONER Please...

Page 2: ...Contents Cautions Introduction to Spare Parts Maintenance Trouble Shooting When Trouble Happens Customer Need to know Installation Procedure 1 5 6 7 8 9 10 11 12 13 14 24...

Page 3: ...ylene and the polyethylene foam pads contain no fluorochloric hydrocarbon Consult your local authorities for the name and address of the waste materials collecting centers and waste paper disposal ser...

Page 4: ...oner Do not put fingers or any other things into the inlet outlet and swing louver Do not allow children to play with the air conditioner In no case should children be allowed to sit on the outdoor un...

Page 5: ...to continue using the conditioner will damage the conditioner and may cause electrical shock or fire hazard When need maintenance and repairment call dealer to handle it Incorrect mainten ance and re...

Page 6: ...tted to placed on or stand on outdoor unit The falling of goods and people may cause acci dents Pets and plants should not be blowed directly in the air flow Otherwise will suffer damage Don t operate...

Page 7: ...high salt content in the air c Near to hot spring with high content of sulfide gases d Area with frequent fluctuation of voltage e g factory etc e In vehicles or ships f Kitchen with heavy oil vapour...

Page 8: ...Introduction to Spare Parts 6 adjust air outlet direction by the air direction adjusting button on remote controller Air ourlet blade Suction grill Air filter located in the suction grill...

Page 9: ...r one time B Wash with water Swing off the water and then place in cool place Pull the two handles at the same time slowly draw them out 2 Dismantle air filter Clip cpening Bottom of filter Frame of a...

Page 10: ...n the air filter indoor unit and outdoor unit and cover the unit with dustcoat Pre season Care See that there is no obstacles blocking the air inlet and air outlet of both indoor and outdoor unit to a...

Page 11: ...tobacco absorbed by indoor unit During operation white fog comes out of indoor unit When in COOL or DRY mode a thin water fog can be seen blown out of unit this is the condensed fog because the sudden...

Page 12: ...et ride of the excess heat indoor fan will continue running for a while after unit autom atically stops Water or vapor generated from the outdoor unit during heating Please check the following things...

Page 13: ...in the room Sunlight direct into the room Too crowed in the room Cooled air blown out when heating When the air conditioner does not operate properly after you have checked the above mentioned items...

Page 14: ...e temp over 120 for 3 times continuously in 30m E5 5 overcurrent Indicate phase failure when been electrified for the first time indicate overcurrent protection during working procedure E6 6 16 High p...

Page 15: ...ter installation please use the air conditioner according to the specification in the operation manual Using Directions Adjust suitable airflow direction Avoid direct sunlight and airflow Keep the pro...

Page 16: ...ife 9 Pincers 10 Leakage detector or soapy water 11 Band tape 12 Scraper 13 Refrigerant oil The installation tools listed in the following sheet can be used as required The following parts mentioned i...

Page 17: ...t falling down may happen Unit should be placed on a place strong enough to hold the unit Or unit will fall down causing injuries When install the unit take in consideration of storms typhoom earthqua...

Page 18: ...ntenance Indoor and outdoor unit piping length is within limit Refer to Installation Manual for outdoor unit Indoor and outdoor unit power cable inter unit cable are at least 1 m away fromT V radio Th...

Page 19: ...g bolts 790 Distance between suspending bolts 890 890 Ceiling opening Ceiling opening A 20 Over drain pipe 950 Ornament panel 890 Ceiling opening 840 Indoor unit 780 Distance between suspending bolts...

Page 20: ...e sure to use nut and washer at both ends of the bracket Fix the bracket firmly 2 Adjust the height and position of the unit Refer to preparation for the installation 1 3 Proceed with 3 and 4 of In th...

Page 21: ...insulator with seal Refrigerant piping 5 19 Table 1 7 Apple refrigerant oil Torque spanner spanner Piping joing Flare nut Clamp Gas pipe Liquid pipe Insulator accessory For liquid pipe Insulator acce...

Page 22: ...uch force on it Installation of water drainage pipe 6 Note 20 Use the self provided stiff pipe and clamp 1 with unit Insert water pipe into water plug until it reaches the white tape Tighten the clip...

Page 23: ...cting hole Watering can of plastic pipe should be about 100 mm long 100mm Water drainage port for maintenance Drain water from this hole Self provided stiff pipe Inspecting hole NOTE L N and 1 2 are e...

Page 24: ...match that on terminal block 1 Prepare ornament panel Handling of ornament panel Ornament panel shall not be placed face down or against wall neither on an uneven object Don t bend carelessly the swi...

Page 25: ...connecting Side of ornament panel Side of indoor unit Check whether indoor unit is horizontal with leveler or polythene pipe filled with water and check that the dimension of the ceiling opening is co...

Page 26: ...ount Unit might fall down make vibration or noise This may lead to gas shortage Dew or water drop may occur Dew or water drop may occur Problem may occur or parts got burned Problem may occur or parts...

Page 27: ......

Page 28: ......

Reviews: