Installation Manual of Room Air Conditioner

1. Piping connection of the outdoor unit

Connecting the connecting pipe and inlet and

outlet liqued pipe according to the piping method.

Purging Method:

Push the air out of the indoor unit
and piping as followes:
(1) Remove the valve cap on 2-way
      valve in outdoor unit.
(2) Loosen by 1/2 turn the flare nut of
     gas pipe, which is conneted to 
     3-way valve.
(3) Loosen 2-way valve by 90

o

 using

     hexagon wrench, and after approx.
     6 sec tighten it up. Gas comes out
     through flare nut on wide pipe. If no
     gas is discharged, tighten flare nut
     with specified torque.
(4) Open 2-way and 3-way valves
      using specified torque.
(5) Tighten the caps on the valves
      with specified torque.

2-way valve

3-way valve

Liquid side

Gas side

Pipe Diameter (

)

Fastening Torque

Liquid Side 6.35mm(1/4")

Gas Side 15.88mm(1/2")

50N.m

18N.m

Forced fastening without careful

centering may damage the

threads and cause a leakage of

gas.

Liquid Side 9.52mm(3/8")

Gas Side 15.88mm(5/ 8")

60N.m

42N.m

15.88mm (5/8")

9.52mm (3/8")

Liquid side

Gas side

2-way valve

3-way valve

Note: When extending piping, air inside piping shall be removed  by using external refrigerant gas, 

charge according to the following list.

Brand new outdoor unit is charged 50g or 80g(22k,24k) more refrigerant than regulated weight. Only for 

first installation, this extra 50g or 80g(22k,24k) can be used to purge airin pipes.

          During this procedure, 50g or 80g(22k,24k) refrigerant will be discharged in piping.(This must be

          strictly controlled within 90

o

 and 10 sec.)

CAUTION

In case more than 5m

Oil trap shoud be installed every 5~7m

Max. Length:       for  7K 9K :       A=7m

                            for 12K:            A=10m

                            for 18K 22K 24K:  A=20m

Max.Elevation:

for  7K 9K 12K: 5m

for 18K 22K 24K: 10m

no more gas if the length of connecting pipe is less than 7m(••7K 9K)

••

or 10m(12K) or 20m(18K 22K 24K).

The height difference between any two indoor or outdoor units can not be 

more than 5m(7K 9K 12K ) or 10m(18K 22K 24K).

A

Outdoor unit

Indoor unit

Outdoor unit

Indoor unit

Oil trap

Summary of Contents for HPU-18C03/E1

Page 1: ...onnecting hose Insulation material Putty Drain hose A B C D E F No Shape and description QTY Remote controller Cement nail Connecting pipe Drain hose Wire clip Rubber pad Non adhensive tape Fixing of the unit 1 Position of the wall hole Wall hole should be decided according to installation place and piping direction refer to installation drawings 2 Making a wall hole Drill a hole of 70X70mm dia wi...

Page 2: ...unit with union of connection pipe Arrange the piping as per the wall hole and bind drain hose connecting electric cable and piping together with polyethylene tape Insert the bound piping connecting electric cable and drain hoes through wall hole to connect with outdoor unit 2 Arrangement drain hose Drain hose shall be placed in under place There should be a slope when arrange drain hose Avoid up ...

Page 3: ...mage the threads and cause a leakage of gas Liquid Side 9 52mm 3 8 Gas Side 15 88mm 5 8 60N m 42N m 15 88mm 5 8 9 52mm 3 8 Liquid side Gas side 2 way valve 3 way valve Note When extending piping air inside piping shall be removed by using external refrigerant gas charge according to the following list Brand new outdoor unit is charged 50g or 80g 22k 24k more refrigerant than regulated weight Only ...

Page 4: ... cable gently to make sure it is tight Replace cover after wiring Wiring of outdoor unit Insert the cable from inside the wall hole where piping already exist Pull it out from front Loose terminal screw and insert cable end fully into terminal block then tighten it Pull the cable gently to make sure it is tight Replace cover after wiring When connecting indoor and outdoor wire check the number on ...

Page 5: ...and test run Please operate unit according to this Manual Items to be checked during test run Please made a in Are there any gas leakage How is insulation at piping connection carried out Are electric wires of indoor and outdoor unit firmly inserted into terminal block Is electric wiring of indoor and outdoor securely fixed Is drainage securely carried out Is earth line grounding securely connecte...

Reviews: