Domestic Air Conditioner
5.1.11 Low load protection control
In order to prevent the frosting of the indoor heat interaction device, the outdoor system will be
stopped if the indoor heat interaction temperature is below zero centigrade for 5 minutes, but the fan
will continue to operate. The outdoor system will be started again when the heat interaction
temperature is above 7 centigrade and the system has been stopped for 3 minutes. The malfunction
will be stored in the malfunction resume and will not be revealed.
5.1.12 High load protection control
The outdoor system will be stopped if the coil temperature is above 65
ć
for 2 minutes. The indoor
fan will be controlled by the thermostat. The outdoor system can be restarted when the coil
temperature is below 42
ć
and the system has been stopped for 3 minutes. The malfunction will be
stored in the malfunction resume and will not be revealed.
5.1.13 abnormal operation of indoor system
When the outdoor system operates, if the indoor system operation differs from the outdoor system,
the abnormal operation malfunction will be reported. 10s after the report, the indoor system will be
closed.
Outdoor system mode
Indoor system mode
conflicts
cooling
heating
yes
cooling
cooling
no
cooling
airflow
no
heating
heating
no
heating
airflow
yes
heating
cooling
yes
5.1.14 Malfunction list resume.
Nothing is presented if there is no code list.
The malfunction display will automatically finish in 10 seconds.
The remote control only receives the sigals for stop. According to the signals, the malfunction resume
presentation finishes.
The resume restores after the power supply restores.
5.1.15 abnormality confirmation approaches.
1. indoor temperature sensor abnormality:
under the operation, the normal temperature ranges from 120 degree to -30 degree. When the
temperature goes beyond this range, the abnormality can be confirmed. If the temperature goes back
into the range, the system will automatically resume.
Summary of Contents for HSU12VHG-B
Page 43: ...Domestic Air Conditioner HSU12 HG DB SM System Configuration 40 ...
Page 71: ...68 Domestic air conditioner Removal of procedure 9 1 HSU12 HG DB SM ...
Page 74: ...71 Domestic air conditioner Removal of procedure three two HOOKS HSU12 HG DB SM ...
Page 76: ...73 Domestic Air Conditioner Removal of procedure 9 4 HSU12 HG DB SM ...
Page 77: ...74 Removal of procedure 9 5 HSU12 HG DB SM Domestic Air Conditioner ...
Page 78: ...75 Domestic air conditioner Removal of procedure 9 6 HSU12 HG DB SM ...
Page 79: ...76 Domestic air conditioner Removal of procedure 9 7 HSU12 HG DB SM ...
Page 80: ...Domestic air conditioner 77 Removal of procedure HSU12 HG DB SM ...
Page 81: ...Domestic air conditioner Removal of procedure 78 HSU12 HG DB SM ...
Page 82: ...79 Domestic air conditioner Removal of procedure HSU12 HG DB SM ...
Page 83: ...80 Removal Procedure 9 HSU12 HG DB SM ...
Page 84: ...81 Removal Procedure HSU12 HG DB SM ...
Page 85: ...Removal Procedure 82 4 HSU12 HG DB SM ...
Page 86: ...83 Removal Procedure HSU12 HG DB SM 9 10 ...
Page 87: ...84 Removal Procedure 11 HSU12 HG DB SM ...
Page 88: ...85 Removal Procedure 12 HSU12 HG DB SM ...
Page 89: ...86 Removal Procedure HSU12 HG DB SM ...
Page 90: ...87 Removal Procedure HSU12 HG DB SM 9 13 ...