Outdoor unit:
Symbols:
MCA: Min. circuit amps. (A)
TOCA: Total over-current amps.(A)
MFA: Max. fuse amps of circuit
breaker
MSC: Max. starting current
RLA: Rated load amps.(A)
OFM: Outdoor fan motor
KW: Rated motor output(KW)
FLA: Full load amps(A)
Notes:
1. RLA is based on the nominal condition
2. Voltage range
The units are applicable for the electrical systems
where voltage supplied to unit is in the range.
3. Maximum allowable voltage unbalance between
phases is 2%.
4. Power supply uses the circuit breaker
units
model
phase FQY voltage
volt.
range
power supply
MCA
TOCA
MFA
compressor
OFM
RLA
KW
FLA
AV08NMVERA
AV10NMVERA
AV12NMVERA
AV14NMVERA
AV16NMVERA
AV18NMVERA
AV20NMVERA
AV22NMVERA
AV24NMVERA
AV26NMVERA
AV28NMVERA
AV30NMVERA
AV32NMVERA
AV34NMVERA
AV36NMVERA
AV38NMVERA
AV40NMVERA
AV42NMVERA
AV44NMVERA
AV46NMVERA
AV48NMVERA
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
380
342-418
342-418
342-418
342-418
342-418
342-418
342-418
342-418
342-418
342-418
342-418
342-418
342-418
342-418
342-418
342-418
342-418
342-418
342-418
342-418
342-418
21.3
23.5
26.3
29.8
32.2
44.8
47
49.8
53.3
55.7
59.6
62
64.4
76.8
79.2
83.1
85.5
87.9
90.7
94.2
96.6
29.5
32.9
36.8
41.7
45
62.4
65.8
69.7
74.6
77.9
83.4
86.7
90
107.5
110.8
116.3
119.6
122.9
126.8
131.7
135
25
25
30
35
35
50
50
55
60
60
70
70
70
85
85
95
95
95
105
105
105
15
17
19
21
23
15+17
17+17
17+19
17+21
17+23
21+21
21+23
23+23
17+17+21
17+17+23
17+21+21
17+21+23
17+23+23
19+23+23
21+23+23
23+23+23
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2