31-5000755   Rev. 0

21

ENGLISH  

INSTALLATION INSTRUCTIONS

Electric Heater (cont)

Oudoor unit, central control and all indoor units are of parallel connection via two lines without polarity.

There are three ways of connecting the line control and indoor units:
A.  One wired control to control multiple units, i.e. 2-3 indoor units, as shown in the above figure, (1-3 indoor units). The 

indoor unit 3 is the wire controlled main unit and others are the wired controlled subordinate units. The remote control 

and the main unit (directly connected to the indoor unit of wired control) are connected via three wires with polarity. 

Other indoor units and the main unit are connected via three lines with polarity. SW01 on the main unit of wired control 

is set to 0 while SW01 on other subordinate units of wired control are set to 1, 2 and so on in turn. (Please refer to the 

code setting A at page 15)

B.  One wired control controls one indoor unit, as shown in the above figure (indoor unit 4-8). The indoor units and the 

wired control are connected via three lines with polarity.

C.  Two wired controls control one indoor unit, as shown in the figure (indoor unit 9). Either of the wired controls can be set 

to be the main wired control while the other is set to be the auxiliary wired control. The main wired control and indoor 

units, and the main and auxiliary line controls are connected via three lines with polarity.

Note:

 For DC motor/low ESP duct type, the PCB comes with the terminal blocks. Please be sure to pay attention to do 

the wiring according to the labels. The power lines and signal lines go through the metal wire hole separately with the 

protective sleeve of the connecting line.

Wire gauge size and breaker size for total indoor amp draw. Current NEC guidelines and local codes will trump this chart.

Items Total 

Current of Indoor 

Units(A)

Cross Section 

AWG (mm

2

)

Length

in.(m)

Rated Current of 

Overflow Breaker (A)

Rated current of 

residual Circuit 

Breaker(A)

Ground Fault 

Interrupter(mA)

Response time(S)

Cross Sectional 

Area of Signal Line

<7 

14(2.5) 

65.6(20) 

10 

10 A,30 mA,0.1S or 

below

16 AWG (1.25mm

2

)

≥7 and <11 

12(4) 

65.6(20) 

15 

15 A,30 mA,0.1S or 

below

≥11and <16 

10(6) 

82(25) 

20 

20 A,30 mA,0.1S or 

below

≥16 and <22 

8(8) 

98.4(30) 

30 

30 A,30 mA,0.1S or 

below

≥22 and <27 

6(10) 

131(40) 

30 

30 A,30 mA,0.1S or 

below

The electrical power line and signal line connections must be tight.
•  Every indoor unit must have a ground connection.

•  The power wire should be size up if it exceeds the permissible length.

•  Shielding of the control wire of all the indoor and outdoor units should be connected together and grounded at one 

point.

•  Signal lines should not exceed 3280ft (1000m)

Summary of Contents for MVAX009ME2AA1

Page 1: ...MVAX009ME2AA1 MVAX012ME2AA1 MVAX018ME2AA1 MVAX024ME2AA1 MVAX030ME2AA1 MVAX036ME2AA1 MVAX042ME2AA1 MVAX048ME2AA1 MVAX054ME2AA1 MVAX060ME2AA1 Design may vary by model number L aspect peut varier selon l...

Page 2: ......

Page 3: ...Serial number _______________________________________ Date of purchase To register your new Haier Duct Free system go to Haierductless com product registration and input the model serial number inform...

Page 4: ...e control system Keep the equipment and its cord out of reach of children Product Features 1 Suspended indoor unit installation saves space 2 Automatic display of error and fault codes Please refer to...

Page 5: ...appliance by a person responsible for their safety Children should be supervised to ensure that they do not play with the appliance To avoid danger of suffocation keep the plastic bag or thin film use...

Page 6: ...ldren should be supervised to ensure that they do not play on or near the equipment Keep the appliance and its power supply wiring out of reach of children This equipment is not intended to be operate...

Page 7: ...rmance Peak pressure of R410A is much higher than R22 Use copper tubing with adequate wall thickness To prevent breaking of the pipe avoid sharp bends Bend the pipe with a radius of curvature of 4 in...

Page 8: ...Btu h 42000 48000 Heating Btu h 46000 54000 Electrical Power supply V Ph Hz 208 230 1 60 208 230 1 60 MCA A MOP A 15 15 ESP in W G 0 3 0 5 0 9 0 3 0 5 0 9 54k 60k Capacity Cooling Btu h 54000 60000 H...

Page 9: ...ECIFICATIONS Unit Dimensions Model Width Depth Height A B 17 1 2 in 445mm 21 in 533mm 47in 1194mm 11 11 16in 297mm 16 1 2 in 419mm MVAX042 048ME2AA1 21 in 533mm 53in 1346mm 20 in 506mm MVAX054 060ME2A...

Page 10: ...onal injury and property damage Select the following places to install indoor units 1 Where there is enough room for the unit above the ceiling 2 Where the drainpipes can be well positioned 3 Where th...

Page 11: ...ncealed area and not accessible to the general public or animals If air handler is installed in the vertical position make sure there is enough room around the unit for service and maintenance The uni...

Page 12: ...8 41 2 3 MODEL DOWNFLOW FRONT LEFT RIGHT BEHIND BELOW ABOVE MVAX009 036ME2AA1 24 19 2 3 34 5 7 21 2 5 MVAX042 048ME2AA1 38 1 6 24 1 7 MVAX054 060ME2AA1 41 2 3 25 5 8 MODEL HORIZONTAL RIGHT FLOW FRONT...

Page 13: ...ontal Right Flow Installation The drain pan needs to be moved from the left side of the coil to catch and drain condensate 1 Detach TC1 and TC2 thermistors ring temperature sensor and thermostat from...

Page 14: ...rmistor and the temperature sensor are on the front of the coil and the second thermistor on the left side 2 Slide coil assembly and both drain pans out of the air handler The side water tray should b...

Page 15: ...ew metal side panels onto coil one on each side 6 Unscrew internal electrical box Loosen the black waterproof cable plug and adjust the harness to allow for more slack in the wires This is required in...

Page 16: ...ould be on the wires There is a lip on the back edge of the metal shelf that aligns with the slot at the bottom of the front of the electrical box 8 Optional If needed install electric heater followin...

Page 17: ...rnal electrical box Loosen the black waterproof cable plug and adjust the harness to allow for more slack in the wires This is required in order to take tension off the cables when the electrical box...

Page 18: ...allation 13 Undo white cable ties along the side of the unit to make room for coil reinstallation 14 Slide the coil back into the unit along the side rails in the orientation shown below Only include...

Page 19: ...ure sensor should be inserted into the upper hole of the evaporator cover with a wire clamp The hole in the front of the triangular plate where the temperature sensor was originally located may remain...

Page 20: ...ve the upper access panel from air handler Remove cover plate from air handler Slide the heater kit into the slot and secure element plate with previously removed screws Insert power leads into the ci...

Page 21: ...other is set to be the auxiliary wired control The main wired control and indoor units and the main and auxiliary line controls are connected via three lines with polarity Note For DC motor low ESP du...

Page 22: ...4 060ME2AA Piping Size in mm Gas pipe 3 8 9 52 5 8 15 88 5 8 15 88 5 8 15 88 Liquid pipe 1 4 6 35 3 8 9 52 3 8 9 52 3 8 9 52 Piping Material R 410a rated seamless copper tubing Connecting Procedures o...

Page 23: ...ill prevent odors from entering indoors or corrupting the unit DO NOT connect the condensate drain pipe into the rain pipe This will prevent rain water from pouring in and causing property loss or per...

Page 24: ...or to servicing any component in the system Wire Connections 1 Connecting ring terminals The method of using circular terminal is shown in the figure Take off the screw connect it to the terminal afte...

Page 25: ......

Page 26: ...er wire shall not be more than 820ft 250m P Q P Q A B C P Q A B C P Q A B C A B C Outdoor Indoor 1 Indoor 4 Indoor 7 Indoor 2 Indoor 5 Indoor 8 Indoor 3 Indoor 6 Indoor 9 P Q A B C P Q A B C P Q A B C...

Page 27: ...s 1 2 3 4 Address of wire controlled indoor unit group address SW03_1 SW03_2 SW03_3 SW03_4 Address of wire controlled indoor unit group address 0 0 0 0 0 wire controlled main unit default 0 0 0 1 1 wi...

Page 28: ...1 0 0 0 0 1 0 2 66 1 1 1 1 1 1 1 63 127 Note Set the address by code when connecting the centralized controller or gateway or charge system Address of centralized controller communication address 0 or...

Page 29: ...Sw5 On Old protocol Off Off Self adaption Sw6 On reserved Off Off reserved Sw7 On Model with Up Down and Left Right swing Off Off Model with Up Down swing Sw8 On Fresh Air unit Off Off General unit Fo...

Page 30: ...ower supply can the operator clean the air conditioner otherwise there is a risk of electric shock or injury Make sure to use a stable platform while cleaning or servicing the equipment Do not flush t...

Page 31: ...ndicator flashes Waiting indicator Displayed when the control is set it to the cooing or heating mode and the current mode of operation is opposite to the requested setting Idle indoor unit still has...

Page 32: ...s fastened Check if the refrigerant and condensation lines are insulated Check if the water is drained to the outside Check if the indoor units are positioned RUN TEST Equipment installers should test...

Page 33: ...r TC1 03 3 Fault of indoor unit pipe temp sensor TC2 04 4 Fault of indoor unit dual heat source temp sensor 05 5 Fault of indoor unit EEPROM 06 6 Fault of communication between indoor outdoor units 07...

Page 34: ...34 31 5000755 Rev 0 ENGLISH NOTES...

Page 35: ...installer s invoice If the installation date cannot be verified then the Date of Purchase will be sixty 60 days after the manufacture date as determined by the Product s serial number You should keep...

Page 36: ...s the District of Columbia and Canada This warranty it provided by GE Appliances a Haier company Louisville KY 40225 The Product is defined as Haier brand Ductless Split Units The Product contains 2 s...

Reviews: