10
49-5000429 Rev. 4
ENGLISH
Save time and money! Review the charts on the following pages first and you may not need to call for service.
Problem
Possible Cause
What To Do
Dehumidifier does
not start
The dehumidifier is unplugged.
Makes sure the dehumidifier’s plug is pushed completely into the
outlet.
The fuse is blown/circuit breaker is
tripped.
Check the house fuse/circuit breaker box and replace the fuse or reset
the breaker.
Dehumidifier has reached its set
humidity level or bucket is full.
The dehumidifier automatically turns off when either condition occurs.
Change to a lower setting or empty the bucket and replace properly.
Bucket is not in the proper position.
The bucket must be in place and securely seated for the dehumidifier
to operate.
Power Failure.
There is a protective time delay (up to 3 minutes) to prevent tripping
of the compressor overload. For this reason, the unit may not start
normal dehumidification for 3 minutes after turning back on.
Dehumidifier does
not dry the air as it
should
Did not allow enough time to
remove the moisture.
When first installed, allow at least 24 hours to maintain the desired
dryness.
Airflow is restricted.
Make sure there are no curtains, blinds or furniture blocking the top or
back of the dehumidifier. See the Choosing a Location section.
Dirty Filter
See the Care and Cleaning section.
The Humidity Control may not be
set low enough.
For drier air, press the
ź
pad and set to a lower percent value (%) or at
NS (Nonstop) for maximum dehumidification.
Doors and windows may not be
closed tightly.
Check that all doors, windows and other openings are securely closed.
Clothes dryer may be blowing
moisure-laden air into the room.
Install the dehumidifier away from the dyer. The dryer should be
vented to the outside.
Room temperature is too low.
Moisture removal is best at higher room temperatures. Lower room
temperatures will reduce the moisture removal rate. Models are
designed to be operated at temperatures above 41°F (5°C).
Dehumidifier runs
too much
Area to be dehumidified is too large.
The capacity of your dehumidifier may not be adequate.
Doors and windows are open.
Close all doors and windows to the outside.
Frost appears on the
coils
Room temperature is below 41°F
(5°C)
Please operate unit at temperatures above 41°F (5°C). Frost will
usually disappear within 60 minutes. Under certain conditions, frost
may appear on the coils of your dehumidifier at temperatures above
41°F (5°C). This is normal and frost will usually disappear within 60
minutes. See the Automatic Defrost section.
Fan noise
Air is moving through the
dehumidifier.
This is normal.
Water on floor
Hose connection may be loose.
Check the hose connection. See the Removing Collected Water
section.
Intended to use the bucket to collect
water, but a hose was attached.
Disconnect the hose if using a bucket to collect water. See the
Removing Collected Water section.
Bucket Full LED light
flashing and alarm
sounds while drain
hose is connected.
Drain hose not tight on fitting.
Check drain hose connection.
Drain hose is kinked.
Ensure the drain hose is pointed straight down to the floor and is not
kinked in anyway.
Bucket fills up when
using drain pump
Unit not in pump mode
Ensure pump is turned on and pump light is illuminated
Pump hose not installed
Ensure pump hose is properly installed on back of unit
Water level sensor issue
This may be caused by very humid conditions or error with float
sensor. Check unit for a P1 error code on display. If this is present -
turn off the unit, unplug unit for a few seconds, plug back in and turn
on the unit to reset sensor. If this error continues to occur refer to
warranty section for exchange options.
TROUBLESHOOTING
Summary of Contents for QPHR50LZ
Page 2: ...2 49 5000429 Rev 3 ENGLISH ...
Page 11: ...49 5000429 Rev 4 11 ENGLISH NOTES ...
Page 14: ...14 49 5000429 Rev 4 ESPAÑOL ...