background image

The factory charge is sufficient for 25 feet of standard liquid line. For longer or shorter liquid line
lengths, adjust the charge as follows:
1/4" Line         +/- 0.3 oz. Per foot
5/16" Line 

+/- 0.4 oz. Per foot

3/8" Line

+/- 0.6 oz. Per foot

1/2" Line 

+/- 1.2 oz. Per foot

Vertical Separation between Indoor and Outdoor Units

Maximum allowable vertical separations between indoor and outdoor units are illustrated in 

Figure

3-A and Figure 3-B

. It's 70' when the indoor unit is below the outdoor unit (Figure 3-A), and 50' when

the indoor unit is above the outdoor unit (Figure 3-B).

To ensure good oil return to the compressor when the indoor unit is below the outdoor unit, suction
line oil trap should be used as illustrated in Figure 3-A.

Tubing Connections

! CAUTION

 - Use extreme caution in removing the caps from the suction and liquid line fittings, as

there is pressure present. A fitting is on the liquid line to remove pressure.

! CAUTION

 - Condensing units are charged with refrigerant. Condensing unit liquid and suction

valves are closed to contain the charge within the unit. Do not force the valve stem against the retaining
ring. If the valve stem is backed out past the retaining ring, system pressure could force the valve stem
out of the valve body and possibly cause personal injury.

! CAUTION

 - The piston is in the accessory bag. Don't forget to take it out and put into the indoor

liquid pipe orifice.
Instructions on the field tubing connections and valve opening procedure are as follow:

Refrigerant Line Sizing

Check the following table (

Table 2

 

) for correct suction and liquid line sizes for any combination of

the unit size and the maximum refrigerant line length.

Table 2:Refrigerant Line Sizing

Unit Size 

(Ton)

Suction

Liquid

Suction

Liquid

Suction

Liquid

Seer

1.5

5/8

3/8

3/4

3/8

3/4

3/8

     

9

/10

2.0

5/8

3/8

3/4

3/8

3/4

3/8

     

9

/10

2.5

3/4

3/8

3/4

3/8

7/8

/

    

 

9

/10

3.0

3/4

3/8

3/4

3/8

7/8

1/2

     

9

/10

3.5

3/4

3/8

7/8

3/8

1 1/8

1/2

     

9

/10

4.0

3/4

3/8

1 1/8

3/8

1 1/8

1/2

     

9

/10

5.0

7/8

3/8

1 1/8

3/8

1 1/8

1/2

     

9

/10

50-74

Refrigerant Line Length(Ft)

Line Outside Diameter(In)

0-24

25-49

6

Summary of Contents for V1124C2H

Page 1: ...1 5 to 5 Tons Models V1118C2H V1124C2H V1130C2H V1136C2H Installation Operation Manual Central Air Conditioner The information contained in this booklet is subject to change without notice V1142C2H V1...

Page 2: ...service personnel for proper installation adjustment and operation of this unit Read these instructions thoroughly before attempting installation or operation Failure to follow these instructions may...

Page 3: ...spection 5 Equipment Protection From Environment 6 Installation 6 1 General 6 2 Unit clearances 6 3 Refrigerant piping 6 4 Electrical wiring 7 System Startup 8 Operation 9 Miscellaneous 9 1 Replacemen...

Page 4: ...Carefully read this manual and any instructions packaged with separate equipment required to make up the system prior to installation Give this manual to the owner and explain its provisions The owne...

Page 5: ...770 770 705 770 770 805 23 23 31 1 2 585 585 805 23 23 27 3 4 585 585 705 23 23 24 585 585 605 23 23 24 585 585 605 23 23 24 585 585 605 23 23 24 585 585 605 31 5 8 31 5 8 30 5 8 31 5 8 31 5 8 34 5 8...

Page 6: ...cal power to the unit before servicing Disconnect power to both the indoor and outdoor units NOTE There may be more than one electrical disconnect switch Failure to shut off power can cause electrical...

Page 7: ...are made from the service access area The most common application will find the unit best located about 10 from back wall with connection side facing the wall This application minimizes exposed tubing...

Page 8: ...t kink or twist the tubing Refrigerant piping should not be installed in a cement slab as this limits access to the refrigerant should a leak be suspected To ensure good oil return to the compressor i...

Page 9: ...are charged with refrigerant Condensing unit liquid and suction valves are closed to contain the charge within the unit Do not force the valve stem against the retaining ring If the valve stem is back...

Page 10: ...ch increases power consumption and reduces performance The presence of moisture in a system can render it inoperable in a very short time Proper evacuation assures a dry uncontaminated system Here is...

Page 11: ...o not connect many devices to one AC outlet It could cause a fire or an electric shock due to defective contact defective insulation exceeding the permissible current etc Perform electrical work accor...

Page 12: ...for disconnecting power service to the unit The condensing unit control wiring requires a 24 Volt minimum 25 VA service from the indoor transformer as shown on the wiring diagram 7 SYSTEM STARTUP 1 Tu...

Page 13: ...it can take up to 2 hours for this overload to reset Make sure overload has had time to reset before condemning the compressor 9 MISCELLANEOUS 9 1 Replacement Parts Contact your local distributor for...

Page 14: ...y tubes Replace coil assembly Low vapor cool Low evaporator airflow Increase blower speed or reduce restriction replace air filter compressor iced Operating below 65 F outdoors Add low ambient kit eva...

Page 15: ...8 COM BL R TRAN COM 230 7 BL 5 3 RD NO GR 8 6 4 OFM M BK BR 6 S R BR L1 L2 GND 60Hz 1PH 208 230V WH BK BCR 1 BK 2 RD BRK BK L2 RD RD FL L1 BK FL USE COPPER CONDUCTORS ONLY WARNING CABINET MUST BE PERM...

Page 16: ...VOLTAGE FACTORY STANDARD FIELD INSTALLED OPTIONAL L1 L3 L1 L2 L3 1 Confirm system selection Optional components may be field or factory installed 2 If LPS and or HPS and or VTS not installed or remove...

Page 17: ...Made in P R C...

Reviews: