Assembly
Information brochure · H-50.2 system components
V02R00 · 1134319 · 2022-11
22
5.4
Information on assembly
Preliminary
information
Before beginning assembly, ensure that the loads being placed
on the structure can be absorbed.
If no corresponding information (documents) is available, then
a structural appraisal that factors in the load-bearing capacity
required will be necessary, and verification must be provided.
If the required verifications (of safe absorption of forces on the
structure) are not kept, then a claim of manufacturer liability in
the event of damage will become difficult to assert.
The operating company then assumes liability.
Assembly personnel
At least two persons are required for assembly of the fall-arrest
system.
The assembly personnel may not be secured to the system be-
ing installed.
An approved attachment point on the building or another struc-
ture must be used in accordance with EN 795.
Information on
assembly on concrete
structures
Only anchor plugs approved under the building regulations
may be used for concrete structures.
In the case of undefined substrata, the attachment system must
be implemented in consultation with the structural engineer.
Requirement for concrete:
a minimum concrete grade of C20/25 is required.
Information on
assembly on masonry
Only anchor plugs approved under the building regulations
may be used for masonry.
In the case of undefined substrata, the attachment system must
be implemented in consultation with the structural engineer.
Anchorage using a through hole with counterplate is also con-
ceivable. This must be agreed with the structural engineer, and
verification must be provided.
NOTE
Prior to assembly of the access ladder, it must be ensured that the
load transmission to the load-bearing structure is guaranteed with
sufficient certainty (consultation with the structural engineer).
Observe the assembly instructions issued by the plug manufac-
turer!