Valve Control

temperature 1

,open motorized valve;when room temperature reach

setting temperature,close motorized valve,fan coil continues to work(it can

be set as fan close together with valve in advanced setting).

Ventilation mode(fan coil unit is not under controlling)

Fan coil unit is under controlling,it is valve and fan coil unit close together.

Key Lock

Function

Key Lock function:if thermostat opens key lock function,no any operation

after 10 minutes will lock keys automatically(screen display “

icon),press “ ” for 5 seconds will unlock(“

disappears)

Door Key

Energy Saving

Mode

(HY08AC-K)

Enter into energy saving mode by door card.When pull out door card,

“ ”door card icon flashing,if thermostat is in cooling mode,temperature

set as 26

automatically,fan run in low speed;if thermostat is in heating

mode,temperature set as 18

automatically,fan run in low speed

Alarm

Sensor occurs fault,thermostat close fan coil and motorized valve and

display“ ” and“E1”and“E2”.

E1:sensor short circuit alarm

E2:sensor open circuit alarm

When temperature higher than 55

displays “HI”when temperature lower

than 0

displays“LO”

Programmable Mode Setting And Working

HY08AC fan coil units thermostat can set different time different temperature;there is

(manual programmable) and

”(cancel programmable) 2 programs can be chosen.

Manual Programmable

Long press “ ”for 3-5 seconds to enter into setting screen,,short press " ”to choose “ ”

and press “ ”to confirm and enter into manual programmable setting.

After enter into manual programmable,To begin with the first period(“

” flashing) of

Monday,press “ ” to confirm,starting time(default 6:00),it can press“ ”or“ ”to adjust by

yourself,press every one time to increase or decrease 30 minutes and then press “ ”,press

“ ”or“ ” to adjust temperature,press “ ” enter into the second period “ ” setting,the

same as above to finish 4 periods setting,then enter into Tuesday setting,the same setting

method as Monday,then finish 7 days setting,no any operation for 5 seconds will save and

exit automatically.

Cancel programmable:long press “ ”for 3-5 seconds to enter into setting screen,short press

“ ” to choose “ ”programmable,press “ ”to confirm and to cancel programmable mode

back to upper setting screen.Press “ ”to choose next setting or waiting for 5 seconds to exit

Default Setting

Period

Period Setting

Default Time

Default Temperature

Monday

To

Sunday

1

06:00

23

2

8:00

26

3

17:30

26

4

22:00

23

Advanced Setting

In turn off state,long press

” for 5 seconds to enter into advanced setting.Press“ ”or“ ”to

set,short press “ ”to next option and press“ ”or“ ”to set

Display

Sign

Setting Options

Data Setting Function

Factory

Default

A1

Measure Temperature Calibration

-9-+9

(Display room temperature,

Press , to calibrate room

temperature)

0.5

Accuracy

Calibration

A2

Children Lock Setting

0:Half Lock;(can turn on/off

and adjust temperature)

1:Full Lock

0

2:Cancel Children Lock

A3

Setting Temperature Lowest Limit

1-25

5

A4

Setting Temperature Highest Limit

30-70

35

A5

Fan Coil Units Control

0=Fan Under Control

1=Fan Isn’t Under Control

0

A6

Timing Turn On/Off Running Way

0=Timing Turn On/Off For

One Time

1=Timing Turn On/Off For

Cycle Running

0

A7

Key Card Status

00:S1 Connect S2 Means

Put-in Card Status;

01:S1 Disconnect S2 Means

Pull-out Card Status.

00

A8

After Door Card Pull Out To Cool

Temperature

Setting Range 22

32

26

A9

After Door Card Pull Out To Heat

Temperature

Setting Range 10

21

18

AA

Valve Output Choose

2: 2Pipes

4:4 Pipes

4

AB

Return To Factory Default Setting

Display A o,Long Press Fan

Key To Return To Factory

Default Setting

Wiring Diagram

Cautions on Installation and Use

1.

To prevent the thermostat display from a high fluctuation, special treatment has been made

to the program. Therefore, it is normal that the thermostat cannot immediately display the

sudden change of temperature.

2.

The thermostat installed on 1.5m above the ground.

3.

For the thermostat installed,please take care not to install it to the wall corner, door /

window side or behind the door or in such unheated area as exterior wall. Avoid hot / cold

air duct, radiator, flue or thermal pipe.

4.

If you have any problem for the installed ,please contact our company hysen, we will make

a demonstration for you

5.

Only the professional technicians are permitted to open the transmitting and receiving box

of the thermostat for installation. When install the power supply, make sure that the power

cable is well insulated.

6.

The thermostat is unrepairable product. The user shall not open the internal circuit board.

7.

HY08AC series thermostat design for the standard 75x75x 35mm wall mount box installed.

Follow the instructions to open the rear cover base, mount it on the wall and wire it.

8.

Before installing the thermostat, make sure that the system is disconnected. The maximum

voltage of the system shall meet the requirements specified in the Instruction Manual (Max.

AC Voltage: 250V).