Setting/Changing the Temperature
CAUTION
The temperature setting range is 100 – 450
°
C (212 – 842
°
F).
●
Attempt to enter a value outside the setting range will cause the display to begin flashing the HUNDREDS digit again.
Reenter a correct value.
●
Both the display temperature and the temperature setting are the temperature at the sensor. (Even with the same
temperature setting, the temperature of the hot air differs depending on the nozzle size.)
Example: Change the temperature setting from 300 to 450
°
C.
Press the button once.
Press the or button.
Press and hold the button
for more than one second.
Press the button once.
Press the button once.
UP
DOWN
Press the or button.
UP
DOWN
1. Insert the control card into the slot in the
front of the unit.
2. Press the
on temperature setting
section for more than one second.
●
The station goes into temperature setting
mode and the HUNDREDS digit flashes on
the display, indicating that the HUNDREDS
digit can be entered.
NOTE:
It can be flashing even though no card in the
unit, but the temperature cannot be set.
3. Enter the HUNDREDS digit.
●
Use the
UP
and
DOWN
buttons to select the
desired value for the HUNDREDS digit.
Only 1, 2, 3, or 4 can be selected. (In
°
F
mode, 2, 3, 4, 5, 6, 7, and 8 can be
selected).
When the desired value is
displayed, press the
button. The TENS
digit begins to flash.
4. Enter TENS digit.
●
Use the
UP
and
DOWN
buttons to select the
desired value for the TENS digit.
Any value
from 0 to 9 can be selected.
When the
desired value is displayed, press the
button. The UNITS digit begins to flash.
5. Enter the UNITS digit.
●
Select the desired value for the UNITS digit
in the same manner as for the TENS digit.
●
Press the
button.
●
The temperature setting is stored in
memory. Heater control begins after the
new temperature setting is displayed.
Remove the control card.
CAUTION
If the power is turned OFF before the temperature
setting procedure is completed, the new setting value
will not be stored in memory.
6