Appendix 3 Error
A3-2
Solution
1) Confirm link unit settings.
(After making settings, cut power to the PLC.)
2) Go to the editor (V-SFT) and confirm the settings in the [Comm.
Parameter] dialog in the [System Setting] menu.
3) If errors only occur from time to time, it is possible that there is a
noise-based communication error.
* If you still cannot solve the error even after following the suggestions above,
contact your local distributor.
Error Message
Contents
Solution
Error code received
An error code was sent to the link unit
by the CPU of the PLC.
Examine the CPU error code and solve the
problem.
Break
The PIC’s SD (TXD) remains at the low
level.
Examine the connection between the PLC’s
SD (TXD) and the V7’s RD (RXD).
Invalid memory
(applicable to
Mitsubishi CPU)
You specified an address that exceeds
the memory range of the PLC that you
are linked to.
Check the type and range of memory that you
set.
Invalid CPU model
(applicable to
Mitsubishi CPU)
The PLC currently being supported
does not have a corresponding CPU.
Confirm whether or not the CPU that you are
using can be used with the V series.
Format
The code of the received data is invalid.
Check 1, 2, 3 described below.
Compare
(applicable to HIDIC
S10)
Transmission data and received data
are different.
Check 1, 2, 3 described below.
NAK
(applicable to
Allen-Bradley PLC)
A NAK code is received.
Check 1, 2, 3 described below.
TNS discrepant
(applicable to
Allen-Bradley PLC)
Transmitted TNS data and received
TNS data are not in agreement.
Check 1, 2, 3 described below.
Communication
error
An unclear communication error is
detected.
Check 1, 2, 3 described below.
Count error
(applicable to
Mitsubishi CPU and
Q link unit)
The expected data amount is different
from the count value.
Check 1, 2, 3 described below.
Command error
(applicable to
Mitsubishi CPU
/Q link unit)
The response code differs from the
expected code.
Check 1, 2, 3 described below.
Invalid cassette
(applicable to
Mitsubishi ACPU)
This cassette is not included in the
memory cassettes currently being
supported.
Contact your local distributor.
Password error
(applicable to
Mitsubishi QCPU)
The password is incorrect.
Contact your local distributor.
Check I/F driver
(for simulator
I/F driver)
Although a request to send is given to
the computer (simulator), no answer is
returned within the specified time.
If a simulator is not used, transfer the I/F
driver for PLC again.
Summary of Contents for Monitouch V Series
Page 1: ...Function Hakko Electronics Co Ltd...
Page 3: ......
Page 11: ......
Page 35: ......
Page 36: ...System Setting...
Page 37: ......
Page 64: ...Basic Functions...
Page 65: ......
Page 95: ...Chapter 2 Overlap 2 30 Please use this page freely...
Page 139: ...Chapter 4 Lamp 4 14 Please use this page freely...
Page 163: ...Chapter 5 Data Display 5 24 Please use this page freely...
Page 191: ...Chapter 6 Message Display Relay Message 6 28 Please use this page freely...
Page 427: ...Chapter 13 Macro 13 44 Please use this page freely...
Page 454: ...Special Functions...
Page 455: ......
Page 507: ...Chapter 18 Video Display V7i Only 18 32 Please use this page freely...
Page 647: ...Chapter 27 E Mail 27 6 Please use this page freely...
Page 667: ...Chapter 28 Web Server 28 20 Please use this page freely...
Page 690: ...Appendix...
Page 691: ......
Page 714: ...Appendix 1 Internal Memory A1 23 A1 System Memory Please use this page freely...
Page 715: ...Appendix 1 Internal Memory A1 24...
Page 737: ...Appendix 3 Error A3 16 Please use this page freely...
Page 745: ......