Appendix 3 Error
A3-4
•
OPCN-1
•
T-LINK
•
PROFIBUS-DP
Error Message
Contents
Solution
I/F Board Err
The I/F unit for OPCN-1 has an error.
Contact your local distributor.
Stat. No. out of range
The port number set by a switch is not
within the setting range (1 to 127).
Specify the port number within the setting
range.
Network Link Error
Cannot connect to the master station in
the network.
Check the condition of the master station
(PLC). Check the network connection.
Network I/O Access
Err
MONITOUCH is about to access
exceeding the set number of
input/output words.
Check the memory for the network I/O in the
screen data file.
Waiting for Reply
1.
Less than “Max_int” time
(communication monitoring time for
salve station) set on the PLC for
OPCN-1 communications
2.
Timeout on the V-SFT editor
(The timeout time can be set from
[System Setting]
→
[Comm.
Parameter] on the V-SFT editor.)
This error is indicated when the
above 1 and 2 are present.
When the “Max_int” time is too long (infinite,
for example) on the PLC, it is not possible to
know whether or not the response from the
PLC is correctly made.
This error message disappears when a
response from the PLC is received within the
“Max_int” time.
Word Writing to Sp.
Relay
(Mitsubishi A series)
Word writing to a special relay (M9000
and later) is attempted.
* Only bit writing is possible for special
relays when connecting with OPCN-1.
Do not attempt to perform word writing to
special relays.
Error Message
Contents
Solution
T-LINK I/F Board Err
The I/F unit for T-LINK has an error.
Contact your local distributor.
Network I/O Access
Err
MONITOUCH is about to access
exceeding the set number of
input/output words.
Check the memory for the network I/O in the
screen data file.
Access denied by
Loader
V7 processing cannot be performed
because the PLC loader is being
accessed. (This error occurs during
program transfer from the PLC loader
for most cases.)
Wait for the PLVC loader to finish processing,
and press the [RETRY] switch on the V7
screen.
Communication Error
Received Code No.
36
The number of monitor registration
points is too small.
Correct the number of monitor registration
points. For monitor registration, refer to the
user manual of the PLC you are using.
Error Message
Contents
Solution
Timeout
“Check” is displayed 2 or 3 seconds
before this error occurs when
connecting V7 and PROFIBUS-DP in
the RUN mode.
The setting for [Own Stat. No.] on V7 is
discrepant with that for [Address] for [V7
series] on the SIMATIC Manager. Check and
correct the setting.
A screen is displayed instantaneously
(= communications performed) before
this error occurs when connecting V7
and PROFIBUS-DP in the RUN mode.
The DB address set on the V7 screen may not
exist on the PLC (memory over). Check the
setting.
Summary of Contents for Monitouch V Series
Page 1: ...Function Hakko Electronics Co Ltd...
Page 3: ......
Page 11: ......
Page 35: ......
Page 36: ...System Setting...
Page 37: ......
Page 64: ...Basic Functions...
Page 65: ......
Page 95: ...Chapter 2 Overlap 2 30 Please use this page freely...
Page 139: ...Chapter 4 Lamp 4 14 Please use this page freely...
Page 163: ...Chapter 5 Data Display 5 24 Please use this page freely...
Page 191: ...Chapter 6 Message Display Relay Message 6 28 Please use this page freely...
Page 427: ...Chapter 13 Macro 13 44 Please use this page freely...
Page 454: ...Special Functions...
Page 455: ......
Page 507: ...Chapter 18 Video Display V7i Only 18 32 Please use this page freely...
Page 647: ...Chapter 27 E Mail 27 6 Please use this page freely...
Page 667: ...Chapter 28 Web Server 28 20 Please use this page freely...
Page 690: ...Appendix...
Page 691: ......
Page 714: ...Appendix 1 Internal Memory A1 23 A1 System Memory Please use this page freely...
Page 715: ...Appendix 1 Internal Memory A1 24...
Page 737: ...Appendix 3 Error A3 16 Please use this page freely...
Page 745: ......