5-4
1. MITSUBISHI PLC
Communication Setting
The recommended communication parameter settings of the PLC and the V7 series is as follows:
A Series Link
*1 Trans. Mode 1: without CR/LF, Trans. Mode 4: with CR/LF
If [Trans. Mode 4] is selected for [Trans. Mode] in the [Comm. Parameter] dialog of the V7 series,
select [MODE4] in the case of RS-232C, or [MODE8] in the case of RS-422.
QnA Series Link, QnH (Q) Series Link
* The maximum baud rate available with the V7 series is 115200 bps. Select the appropriate baud
rate depending on the used PLC and environment.
A Series CPU, QnA Series CPU
Communication parameters for the V7 series are automatically set.
Item
Setting on PLC
V7 Comm. Parameter Setting
Baud rate
19200 bps
19200 bps
Port
0 for both stations
×
10,
×
1
0
Parity
Even
Even
Transmission
mode
*1
RS-232C
MODE1
Trans. Mode 1
RS-422
MODE5
Trans. Mode 1
Transmission code
Data length
7
7
Stop bit
1
1
Sumcheck
Provided (fixed)
−
Write while running
Possible (fixed)
−
Terminating resistance at sender
Provided (fixed)
−
Terminating resistance at receiver
Provided (fixed)
−
Item
Setting on PLC
V7 Comm. Parameter Setting
Baud rate*
19200 bps
19200 bps
Port
0 for both stations
×
10,
×
1
0
Parity
Even
Even
Transmission mode
RS-232C
MODE5 (binary mode) (fixed)
−
RS-422
Transmission code
Data length
8 (fixed)
−
Stop bit
1
1
Sumcheck
Provided (fixed)
−
Write while running
Possible (fixed)
−