3
1. Error Messages
3-7
Er
ro
r Hand
ling
166
The function set for the serial port is duplicated.
The sub-item number denotes the ports as
shown below:
0: CN1
1: MJ1
2: MJ2
Specify a unique function (simulator, etc.) for
each port.
174
The I/F driver that does not support ladder
communication is set.
Check that the I/F driver supports ladder
communication.
183
The printer model is not correctly set.
Transfer the printer driver suitable for the model
set in the screen program.
184
Printer driver is not found.
Transfer the printer driver.
187
Periodical writing or synchronized writing is set
in the device memory map number specified in
the [Logging Server] window.
Check the data in the device memory map.
188
The same device memory address is specified
for writing in the device memory map number
set with periodical writing or synchronized
writing.
Check the data in the device memory map.
189
The Japanese conversion program is not
registered in MONITOUCH.
Transfer the Japanese conversion program.
192*
I/F driver setting error
Contact your local distributor.
193*
The common data sheet setting is not
registered.
194*
The memory card setting is not registered.
195*
V-I/O input/output device memory is not
registered.
196
Data stored in the storage device is different.
This error may be relevant to the operation for
storing data (screen, 3D parts, etc.) in a storage
device.
Connect a storage device in which data has
been stored correctly using the storage
manager.
199
Multiple functions are assigned to the USB port.
Multiple functions are assigned to the USB-B
port. Use the USB-B port only for any of the
following functions: USB simulator, PictBridge
printer, or USB ladder communication function.
201*
Total byte count error
Contact your local distributor.
207
No video unit is installed.
Install an option unit “GUR-00”, “GUR-04”, or
“GUR-10”.
209
PLC ladder data is not registered.
Transfer the ladder data.
216
A data sheet includes an item that cannot be
printed.
Recheck the data sheet screen. Remove the
unusable item.
217
The source voltage of the touch panel does not
conform to the specifications.
Check the source voltage. For details on the
power source specifications, refer to the V9
Series Hardware Specifications manual.
301
Recipe setting error
Check the recipe settings.
The specified value is outside the permissible
range, or there is a problem with the record
name specification method.
302
The maximum capacity of the alarm server has
been exceeded.
The capacity of DRAM specified under [Internal
Storage Setting] in the [Alarm Server] window
has exceeded the maximum available capacity.
Reduce the number set for [Number of
Monitoring Alarms] or [Number of Data to Save].
Error No.
Contents
Solution
Sub-item number
Error : 166 (Header : x)
V9_Maintenance_E.book 7 ページ 2014年6月2日 月曜日 午前9時45分
Summary of Contents for Monitouch V9 Series
Page 1: ...Troubleshooting Maintenance Manual ...
Page 9: ...11 Before Operation 2 Function Switches 3 System Menu 4 Status Bar MONITOUCH Operations ...
Page 33: ...1 24 4 Status Bar Please use this page freely ...
Page 94: ...2 60 3 Handling Data Changed in Local Mode Please use this page freely ...
Page 95: ...31 Error Messages 2 Troubleshooting Error Handling ...