3-2
1.
Error
Messages
2-1.
Error Numbers
Check the contents of the error (= error number) according to the item name and sub-item number,
and remove the error.
* Error numbers with “*” do not occur under ordinary circumstances.
If any of these errors are displayed, contact your local distributor (specified on the back
cover).
Error No.
Contents
Solution
3
Data version does not match the MONITOUCH
system program version.
Transfer the MONITOUCH system program
from the V-SFT editor.
If the problem persists, check the editor version
and the system program version of the V9
series, and contact your local distributor.
10
The communication I/F unit is not installed, or it
does not match the I/F driver.
Install the communication I/F unit.
Transfer the I/F driver again.
11
The PLC model set in the screen program does
not match the I/F driver.
Check the PLC model and transfer the I/F driver
again.
12
The I/F driver version does not match the
screen program version.
Check the editor version and the I/F driver
version, and contact your local distributor.
13
The I/F driver version does not match the
version of the MONITOUCH system program.
Check the I/F driver version and the system
program version of the V9 series, and contact
your local distributor.
15
The interface language on MONITOUCH does
not match the language set in the screen
program.
Check the MONITOUCH model and the
language set in the created program.
17
The network I/O number exceeds the usable
number range.
Set a number within the usable range.
19
An I/F driver that is unsupported on
MONITOUCH is transferred.
Transfer the correct I/F driver.
20
The maximum capacity of the logging server
has been exceeded.
The capacity of DRAM specified under [Internal
Storage Setting] in the [Logging Server] window
has exceeded the maximum available capacity.
Reduce the number set for [Number of Data to
Save].
22
The logging/alarm block number specified for a
trend or alarm part has not been set.
Select [System Setting]
[Logging Server] or
[Alarm Server], and set the corresponding block
number again.
23*
Memory card file number error
Contact your local distributor.
25
Too many logging entries in the logging server,
or too many alarms monitored by the alarm
server
Check the number set for [Number of Logging]
in the [Logging Server] window or [Number of
Monitoring Alarms] in the [Alarm Server]
window.
[Number of Logging]: Max. 256 words
[Number of Monitoring Alarms]:
Max. 1024 words
27*
An error was found in the logging server or
alarm server.
Contact your local distributor.
28
The same function is set for both MJ1 and MJ2
ports.
Check the settings in the [Hardware Setting]
window and specify correctly.
Sub-item number (Refer to page 3-8.)
Item name (Refer to page 3-8.)
Error number
Summary of Contents for Monitouch V9 Series
Page 1: ...Troubleshooting Maintenance Manual ...
Page 9: ...11 Before Operation 2 Function Switches 3 System Menu 4 Status Bar MONITOUCH Operations ...
Page 33: ...1 24 4 Status Bar Please use this page freely ...
Page 94: ...2 60 3 Handling Data Changed in Local Mode Please use this page freely ...
Page 95: ...31 Error Messages 2 Troubleshooting Error Handling ...