3
1. Error Messages
3-3
Er
ro
r Hand
ling
29
The memory capacity is insufficient.
Reduce the number set for [Number of Data to
Save] under [Internal Storage Setting] or
[Number of Monitoring Alarms] in the [Alarm
Server] window.
Delete the following settings if not necessary.
• Multi-link/Multi-link2
• Ladder monitor
• Connected devices not in use
If the problem persists, contact your local
distributor.
30
The number of registered items is too many.
Reduce the number of items.
31
The memory capacity for the registered items is
insufficient.
Take the following action for the relevant
screen.
Reduce the number set for [Number of
Monitoring Alarms] in the [Alarm server]
window.
Reduce the number of items placed on the
screen.
32
The number of items that uses the memory
exceeds the available number.
Reduce the number of items.
33
The maximum number of switches and lamps
that can be set has been exceeded.
The number of switches and lamps placed on
the screen has exceeded 4096. Switches and
lamps on overlap displays are included in this
number.
Reduce the number of switches and lamps.
34
The items that occupy the memory area exceed
the available work memory capacity.
Reduce the amount of data.
35*
Variable length data error
Contact your local distributor.
36*
ITEM error
37*
Component ITEM error
38*
Component error
40*
Group byte count error
41*
Recognition flag error
42*
Function ITEM error
43*
Function ITEM end error
44*
Group ITEM end error
46
An unavailable device memory address is set or
the available device memory range is
exceeded.
Check the device memory setting.
47
IDs of the items having setting limitations in the
screen library are duplicated on a screen.
Check the IDs and keep them unique.
49*
Group ITEM error
Contact your local distributor.
50*
Link ITEM error
51*
Editor ITEM error
52
The overlap ID is incorrect and must be a value
from “0” to “9”.
Check the overlap ID and set correctly.
53
An overlap library number with no part
registered is specified in the call-overlap setting.
Specify an overlap library number with a part
registered.
55*
Multi-overlap header error
Contact your local distributor.
56*
Graphic undefined command error
57*
Graphic ITEM error
58*
Graphic execution error
59*
Switch function error
60
Switch operating area error
Reset the switch operating area.
Error No.
Contents
Solution
Summary of Contents for Monitouch V9 Series
Page 1: ...Troubleshooting Maintenance Manual ...
Page 9: ...11 Before Operation 2 Function Switches 3 System Menu 4 Status Bar MONITOUCH Operations ...
Page 33: ...1 24 4 Status Bar Please use this page freely ...
Page 94: ...2 60 3 Handling Data Changed in Local Mode Please use this page freely ...
Page 95: ...31 Error Messages 2 Troubleshooting Error Handling ...