3-4
1.
Error
Messages
61*
Statistic graph % display No. exceeding
Contact your local distributor.
62*
Multi data exceeding
63
The ordinal number for data block selection (a
maximum of four) is duplicated.
Check the ordinal number for data block
selection, and set correctly.
64*
Data display element No. error
Contact your local distributor.
65
The scale or graph is not set correctly in the
trend part settings.
Correct the settings for [Scale Max. Value] and
[Scale Min. Value] or [Graph Max. Value] and
[Graph Min. Value] in the [Detail] window.
66*
Internal circle radius is “0”.
Contact your local distributor.
67*
The number of points to display is equal to or
smaller than zero.
68
The display area is insufficient for the area
(lines) that is displayed by one bit (bit order
alarming).
Check the value specified for [Message Lines]
in the [Alarm Server] window, and enlarge the
display area.
69
A pattern or frame larger than the screen size
has been specified.
Re-set the pattern or frame.
70
Too many columns or lines on the data sheet
Check the data sheet columns/lines, and set
correctly.
72
The setting for real time printing of the alarm
part has exceeded the upper limit, or the
specified alarm block number is not unique.
There are four or more alarm parts with [Use the
real-time printing function] selected. Or, there
are two or more alarm parts for which the same
[Alarm Block No.] is set with [Use the real-time
printing function] selected.
Select the [Use the real-time printing function]
setting within the limitations. If the problem
persists, check the editor version and the
system program version of the V9 series, and
contact your local distributor.
73
There are four or more video parts on one
screen. (Including the screen library)
Check the number of video parts and reduce the
number.
74
An animation part is placed in the area other
than the base screen (screen library, etc.).
Place the animation part on the base screen.
75
The model selected in the screen program is
not consistent.
Transfer the system program of the V9 series
from the editor.
77*
Expanded graphic ITEM error
Contact your local distributor.
78*
Expanded function ITEM error
79
Component parts occupy too much memory
capacity.
Reduce the number of component parts.
80*
Macro: Undefined command error
Contact your local distributor.
81
Macro: The numbers of FOR and NEXT
commands are not the same. FOR-NEXT
commands are nested beyond 8 levels.
Correct the FOR-NEXT commands.
82
Macro: There are two different commands for
the same label number.
Macro: Re-set the label.
83
Macro: There is no destination label for the
jump.
Macro: Change or set the destination label.
84*
Macro: Incorrect use of device memory
Change the macro command.
85*
Macro: Undefined system call
Contact your local distributor.
90
Unregistered screen library is used.
Check the screen library number.
91
Bitmap data for a switch or lamp is not
registered.
Check the following points:
No bitmap name is designated.
The part size is too large.
There is no bitmap file in the [Parts] folder
located under [MONITOUCH]
[User].
92*
Multi-language initial display string No. error
Contact your local distributor.
94
Multi-language selection string number error
Error No.
Contents
Solution
Summary of Contents for Monitouch V9 Series
Page 1: ...Troubleshooting Maintenance Manual ...
Page 9: ...11 Before Operation 2 Function Switches 3 System Menu 4 Status Bar MONITOUCH Operations ...
Page 33: ...1 24 4 Status Bar Please use this page freely ...
Page 94: ...2 60 3 Handling Data Changed in Local Mode Please use this page freely ...
Page 95: ...31 Error Messages 2 Troubleshooting Error Handling ...