SmartFOAM
Figure 50: SmartFOAM Power and Ground Connections (6.5 12VDC)
MOTOR GROUND / PRIMARY POWER
CAUTION!
CONNECT THE PRIMARY POSITIVE LEAD FROM
THE TERMINAL BLOCK TO THE MASTER SWITCH
TERMINAL OR RELAY TERMINAL USING AWG TYPE
SGX (SAE J1127), CHEMICAL RESISTANT, BATTERY
CABLE PER Table 6 OF THIS MANUAL AND PRO-
TECT WITH WIRE LOOM.
PREVENT CORROSION OF POWER AND GROUND
CONNECTIONS BY SEALING THESE CONNECTIONS
WITH THE SILICONE SEALANT PROVIDED.
GROUND CONNECTION
Be sure the Hale SmartFOAM system is grounded to the
chassis. Use a short length of wide flat ground strap at
least 1-1/4” (32 mm) wide and less than 18” (457 mm)
long to reduce the potential of RFI emitted by this con-
nection.
A stud is located on the mounting base to attach the
chassis ground strap to the Hale SmartFOAM system
(
, or
When making the ground strap connections make sure
lugs are soldered to the strap ends for trouble free con-
nections. Seal all connection against corrosion.
When the length of the ground strap exceeds 18” (457
mm) use a wider strap or a double thick strap.
CAUTION!
DO NOT CONNECT THE MAIN POWER LEAD TO
SMALL LEADS THAT ARE SUPPLYING SOME OTHER
DEVICE, SUCH AS A LIGHT BAR OR SIREN, AS THE
SMARTFOAM SYSTEMS HAVE A LARGE CURRENT
DRAW.
PRIMARY POWER SUPPLY CONNECTION
Ensure adequate switched electrical power from the bat-
tery positive (+) terminal to the “IN” connection stud on
the motor controller is provided (
mended Primary Power Cable Sizes
).
Use type SGX (SAE J1127) battery cable directly to the
battery, battery switch or solenoid. DO NOT connect
power to the same connection as the pump primer.
When connecting the 12 V 6.5 system with the converter
located remote, wire the converter input and converter out-
put using
Table 6: Recommended Primary Power Ca-
RFI / EMI
Proper installation of system components and cables
along with proper grounding will limit radio interference
caused by the Hale SmartFOAM system. Additionally,
make sure radio cables and hardware are not located in
the immediate area where Hale SmartFOAM equipment
is mounted.
Making round coils of extra control and flow sensor ca-
bles in the pump compartment can act as an antenna.
While the control and flow sensor cables cannot be
shortened, various lengths of cable are available to mini-
mize the “extra” cable in the truck.
Summary of Contents for MiniCAFS 2.1A
Page 3: ...Page 2 SmartFOAM NOTES...
Page 16: ...Page 15 SmartFOAM SYSTEM DIAGRAM Figure 6 Typical Hale SmartFOAM 2 1A and 1 7AHP System...
Page 17: ...Page 16 SmartFOAM Figure 7 SmartFOAM 3 3 5 0 6 5 Single Tank System with In line Strainer...
Page 18: ...Page 17 SmartFOAM Figure 8 SmartFOAM 3 3 5 0 6 5 Single Tank withMSTandIn lineStrainer...
Page 19: ...Page 18 SmartFOAM Figure 9 SmartFOAM 3 3 5 0 6 5 Single Tank withMSTandFSSeriesStrainer...
Page 20: ...Page 19 SmartFOAM Figure 10 SmartFOAM 3 3 5 0 6 5 Dual Tank withMDTIIandIn lineStrainers...
Page 21: ...Page 20 SmartFOAM Figure 11 SmartFOAM 3 3 5 0 6 5 Dual Tank withMDTIIandFSSeriesStrainer...
Page 22: ...Page 21 SmartFOAM Figure 12 SmartFOAM 3 3 5 0 6 5 Dual Tank withADTandIn lineStrainers...
Page 23: ...Page 22 SmartFOAM Figure 13 SmartFOAM 3 3 5 0 6 5 Dual Tank withADTandFSSeries Strainers...
Page 48: ...Page 47 SmartFOAM Figure 28 Typical 4 Inch Check Valve Installation Midship Pump...
Page 59: ...Page 58 SmartFOAM Figure 43 ADT Option Air Hose Connections Part 2...
Page 68: ...Page 67 SmartFOAM Figure 55 Top Mount Low Level Sensor Assembly...
Page 77: ...Page 76 SmartFOAM NOTES...
Page 90: ...89 Page 89 SmartFOAM NOTES...