Configuration
3
1.4.2
X2 Ethernet
Connector X2 is a standard RJ45 Ethernet plug. Only one LED is available for indicating traffic (green
LED).
The connectors pinout is according to the 100Base-TX standard.
1.4.3
Diagnostic LED’s A/B
There are two LED’s for visual indication of the operation mode of the BG02_EIP interface card:
-
LED A: Ethernet/IP connectivity: This LED indicates the operating state of the Ethernet/IP
interface. The following states are shown:
o
Green blinking: Ethernet/IP master connected and data exchange running
o
Green/Red blinking: Ethernet/IP master connected, but data exchange not active.
Either the master is not yet configured or it is not configured correctly (wrong
assembly instance or attribute size defined for data exchange).
o
Red blinking: no Ethernet/IP master connected.
-
LED B: SMpdp/IMpdp connectivity: This LED indicates the operating state of the SMpdp
interface:
o
Green blinking: Everything ok, data exchange running
o
Green/Red blinking: SMpdp physical connection detected, but no data exchange
running. This indicates a problem with the SMpdp configuration.
o
Red blinking: no communication with the SMpdp module possible. Check cable and
station address setting inside the BS300 software (station address of SMpdp must be
set to 3).
After switching on the power supply, the LED’s will do a “lamp test” after a approx 4-5 seconds
bootup delay. For a duration of 2 seconds both LED’s should then run off – red – green – orange
cycles.
2
Configuration
2.1
BG02-EIP configuration
2.1.1
BG02-EIP factory defaults
By default, the BG02-EIP is shipped with the Network configuration set to use DHCP for dynamic
address assignment (according to the ODVA recommendation for Ethernet/IP adapters). If no DHCP
server is found, a link local address from the 169.254.x.y network is used.