background image

 

12 

with these instructions. An adequate chimney or venting system is one that is sealed and lined with the 
capability of producing a -.04" W.C. flue draft and having the capacity to handle the amount of flue 
gas that is introduced.  A chimney with an internal construction of corrosion resistant tile, stainless 
steel, or some other material that will withstand flue gas temperatures up to 1000

0

F is required. 

 

Masonry and metal chimneys shall be constructed in accordance with applicable building code 
requirements.  Masonry chimneys shall be lined with an approved clay tile liner or a listed chimney 
lining system installed in accordance with manufacturers’ instructions and also meeting the 
requirements of NFPA-211 Standard for Chimneys, Fireplaces, Vents, and Solid Fuel-Burning 
Appliances.  Metal chimneys also shall meet the requirements of NFPA-211.  Factory built chimneys 
shall be listed and shall be installed in accordance with their listing and NFPA-211.  

 

Prior to installation of the furnace, the chimney or venting system shall be examined by the installer 
and determined to be in good condition. All joints of the chimney must be tightly sealed. The inside of 
the chimney should be free of all obstruction, such as loose brick, broken pieces of tile, or corroded 
metal. If chimney flues are divided or there are multiple flues within one chimney, make sure there are 
no openings in the partition separating the divided or individual flues.  When a new appliance is 
connected to an existing chimney, that chimney shall be brought up to current requirements.  
Chimneys which are relined shall be done so with an approved liner that will resist corrosion, 
softening, or cracking from the flue gasses. 

 

All chimney clean-out doors and flue connections must fit tightly so they will seal to avoid air 
leakage. 

 

The inside area of the chimney liner

 

should equal, at a minimum, the area of the vent pipe exiting the 

furnace.  If more than one appliance is installed, the area of both appliances shall be used in 
determining the required inside area of the chimney. 

 

The flue gas exit of a chimney shall be at least 3 feet above the highest point where it passes through 
the roof of a building and at least 2 feet higher than any portion of a building within 10 feet of such 
chimney. 

 

The chimney height will also be determined by the height of the surrounding trees, buildings and 
terrain.  When chimney downdraft conditions cause faulty operation that creates a hazard, corrective 
steps must be taken. 

 

When altering the surrounding obstructions is not possible, a chimney cap  can be constructed on the 
top of the chimney to avoid downdrafts. The chimney cap should be pyramid shaped on the top with a 
perfectly flat surface immediately above the chimney outlet. The hood should be attached by four (4) 
iron supports. The four iron supports should be equal in height to the width of the chimney opening. 
Four plates, flaring down, can be added to help insure that the wind will pass straight over the 
chimney outlet.  

 

Chimney Relining 

A tile lined masonry chimney serving an oil fired furnace should comply with applicable building 
codes such as NFPA-211.  An additional listed lining may be required to reduce transient low draft 
during startup and acid water condensation during cyclic operation.  This is particularly true for high 
mass masonry chimneys serving oil fired furnaces of higher efficiency.  For masonry chimneys, local 
experience can indicate how well construction has withstood the lower temperatures produced by 
higher efficiency furnaces. 

 

 

Summary of Contents for HBD1 15

Page 1: ...n and Operation Instruction Manual Variable Speed 2 Stage ECM Motor Keep these instructions with the furnace at all times for future reference Boyertown Furnace Co PO Box 100 Boyertown PA 19512 610 36...

Page 2: ...our oil fired furnace is designed to burn No 1 and No 2 heating oil only Never use gasoline or a mixture of gasoline and oil Do not store gasoline or other flammable vapors and liquids in the vicinity...

Page 3: ...Venting Chimney Relining Chimney Connector Power Venting Vent Dampers Ventilation and Combustion Air 14 Burner Installation 15 Wiring 16 Power Thermostat Oil Tank and Piping 19 Start Up 20 Start Up Eq...

Page 4: ...24 53 37 1 2 12 10 27 5 8 2 2 22 LB D 115 1 40 00 0 115 0 00 6 80 0 2 0x2 0 150 0 16 00 4 435 4 5 24 42 38 1 2 12 10 20 2 2 22 LB D 85 1 05 00 0 88 00 0 6 82 6 1 6x2 0 117 5 14 00 3 1 2 385 4 2 23 38...

Page 5: ...such installation provided the floor under the furnace is protected in accordance with the requirements of accepted building code practice and NFPA 31 The furnaces shall be permitted to be placed on...

Page 6: ...Rear Sides Above Rear Sides 3 thick masonry wall without ventilated air space N A 12 N A 9 N A 6 N A 5 insulation board over 1 glass fiber or mineral wool batts 12 9 9 6 6 5 4 3 24 gauge sheet metal...

Page 7: ...avoid condensation in the furnace heat exchanger The evaporator coil must be installed at least 6 above the heat exchanger for proper air flow Distances less than 6 will result in decreased air flow...

Page 8: ...Area Sq In 600FPM Area Sq In 800FPM Area Sq In 1000FPM Area Sq In 1200FPM Area Sq In 1600FPM Area Sq In 2000FPM 50 12 100 24 18 14 12 150 36 27 22 18 14 200 48 36 29 24 18 14 250 60 45 36 30 23 18 30...

Page 9: ...mode of operation the blower is to run Air flow rates in the different modes are controled by the setting of the DIP switches Standby Mode The thermostat inputs are being continuously monitored The m...

Page 10: ...hange the air flow settings until the blower has come to a complete stop No change in air flow will occur unless the motor has been allowed to a complete stop See figure below for the location of the...

Page 11: ...5 COOL 6 Y1 7 ADJUST 8 OUT 9 O 10 BK PWM 11 HEAT 12 R 13 EM W2 14 Y Y2 15 G 16 OUT Power connector Signal connector Figure 1 Figure 3Power Connector VENTING Failure to follow all instructions can res...

Page 12: ...cracking from the flue gasses All chimney clean out doors and flue connections must fit tightly so they will seal to avoid air leakage The inside area of the chimney liner should equal at a minimum th...

Page 13: ...tor shall not exceed 10 feet The chimney connector shall be installed so as to minimize the number of elbows and to avoid sharp turns or other construction features that would create excessive resista...

Page 14: ...side wall by using a listed power side wall Venter The vent device must be able to produce a draft of 02 W C over the fire and be equipped with a post purge timer set to a minimum time of 5 minutes T...

Page 15: ...from its shipping carton and inspect thoroughly Verify that the correct burner combination and nozzle is installed in the burner as shipped Read the oil burner manual included in the shipping carton a...

Page 16: ...ments 2 Delavan nozzle 3 Hago nozzle Wiring Electric shock hazard can cause severe personal injury or death if power source including service switch for the furnace is not disconnected before installi...

Page 17: ...17 17...

Page 18: ...ed for AC operation the B terminal is for the reversing valve energized for HP operation When wiring for the first stage cooling choose the appropriate Y1 terminal for the air flow required When insta...

Page 19: ...and across ceiling or floor joists Piping shall be supported and protected from physical damage and where necessary protected against corrosion as per code Piping systems shall be maintained liquid t...

Page 20: ...l residue or foreign materials and that the refractory chamber has not been damaged 4 Check oil burner nozzle to ensure that the right size and type is installed and tight in the adapter See prelimina...

Page 21: ...tings shown in Table 8 thru Table 10 are approximate The burner must be adjusted during actual field installed conditions Failure to do so will result in poor performance and nuisance service calls Af...

Page 22: ...r or appliance The area around the furnace should be kept clear of all combustible materials Never attempt to burn garbage or refuse in the furnace Never attempt to light the furnace by throwing burni...

Page 23: ...ay pattern Perform the combustion checks as per the burner manual and the furnace manual Blowers Direct Drive Clean inspect blower wheel annually Lubricate blower motor as per the motors recommendatio...

Page 24: ...504100 504500 11 1 POUCHPLATE GASKET KIT 489000 489000 12 1 BAFFLE ASSEMBLY KIT 730317K 730317K 13 1 HEAT EXCHANGER KIT 730051K 730061K 14 1 FLUE COVER 740800 740800 15 1 REAR PANEL 504130 504530 16...

Page 25: ...LB REAR AIR BAFFLE 504910 504910 14 1 SEPARATION PLATE 740763 740763 15 1 FLUE EXTENSION PIPE 732690 732691 16 1 REAR PANEL 504030 504430 17 1 FLUE COVER 740800 740800 18 1 DOOR 504040 504440 19 1 BLO...

Page 26: ...es Oil Filter Clean Replace Oil Filter Pump Strainer Clean Clean or Replace Strainer Adjust Pressure Per Set up Label Refer to Burner Manual Pump Pressure Per Set up Label Spark Established Ignition E...

Page 27: ...lts at Furnace 120 Volts at Burner Control Adjust Thermostat Check Supply Fuses and Disconnects Fan and Limit Operational Refer to Burner Manual Burner Off on Safety Refer to Burner Manual No No No No...

Page 28: ...erify Correct Furnace Wiring Repair Wiring Replace Power Cord Yes 24 Volts R C on Terminal Strip Yes Replace Fan Center Relay No Check Wiring Replace Cable Place Jumper on R W 24VAC BetweenPins 1 2 Ch...

Page 29: ...ger Proof of purchase will be required of the original purchaser when the claim is made The purchaser must pay all other costs of warranty services including labor costs involved in diagnostic calls o...

Page 30: ...air flow and ACCA Manual D t Work All ducts sealed and insulated as required Burn Burner Model __________________ Nozzle _______GPH _______Deg _______Type_______ er Operation Burner Pump Pressure ___...

Page 31: ...31...

Page 32: ...Serial Number ________________________ Name of Purchaser _________________________________________________________________________ Purchaser s Address ________________________________________________...

Reviews: