Another option for simple, fast and secure project planning is the use of the
TITANUS
®
PipeXpress
software.
TIP
5.2 Project planning guidelines
The knowledge of specific factors is essential in order to carry out project
planning in accordance with AS ISO 7240
‑
20. These are the requirements for
the sensitivity of the system, the number of aspiration apertures and the
accessories necessary for the corresponding application. The pipe system
layout in compliance with the standard can be determined based on these
factors using the following chapters and the project planning table in the
annex.
5.2.1 Determination of necessary pipe accessories
Due to the fact that accessory components (e.g. filters) have a certain
influence on the dimension of pipe project planning, the accessories for the
corresponding application must be selected in advance. An upgrade (e.g.
with a finer filter) is usually only possible if a certain reserve is planned in
advance.
If components are used that have not been approved by the
WAGNER Group GmbH, there is no conformity according to AS ISO 7240-
20.
The condensate separator type KA
‑
1 and the silencer type SD
‑
1 can be
used without restricting project planning.
The following accessory components must be considered:
▪ Air filter
▪ Condensate separator type KA
‑
DN
‑
25
▪ Stop valve for VSK (for automatic air purge system)
▪ Detector box