background image

MANAGEMENT

SYSTEMS

Assessed to ISO 9001:2008

Cert/LPCB ref. 010

Assessed to ISO 14001:2004

Cert/LPCB ref. 010 EMS

MANAGEMENT

SYSTEMS

Cert/LPCB ref. 010

PRODUCT

CERTIFICATION

36 Brookside Road, Havant
Hampshire, PO9 1JR, UK.

Tel: +44 (0)23 9249 2412

Fax: +44 (0)23 9249 2754

Email: sales@apollo-fire.com
Web: www.apollo-fire.co.uk

Series 65

Marine Base Mounted UV Flame Detector

Product overview

Product 

Marine Base Mounted UV Flame       

                                                      Detector

Part No. 

55000-026MAR

PP5071/2017/Issue 1

Page 1 of 2

© Apollo Fire Detectors Limited 2017

Technical Data

All data is supplied subject to change without notice. Specifications are 

typical at 24 V, 25°C and 50% RH unless otherwise stated.

Supply voltage

17 - 28 V dc

Quiescent current

550 µA

Alarm voltage

6 to 33 V dc

Alarm current

61 mA at 28 V
54 mA at 24 V
20 mA at 10 V

Terminal functions

L1 in and out
L2
-R

Supply positive
Supply negative
Remote indicator 
negative 
connection

Remote output characteristics

Remote is a current sink to the negative 
line limited to 17 mA

Alarm indicator

Red light emitting diode (LED)

Design alarm load

420 Ω in series with a 2  V drop

Holding voltage

6 V min

Holding current

10 mA min

Minimum voltage required to 
illuminate indicators

12 V

Alarm reset voltage

< 1 V

Alarm reset time

1 second

Range of view

0.1 m² n-heptane at 25 m

Sensitivity

Class 1, EN 54-10

Field of view

90º cone

Spectral response

UV 180 to 260 nm

Operating temperature                 
(no condensing or icing)

-40ºC to +70ºC

Storage temperature

-40ºC to +85ºC

Relative humidity

95% non-condensing

IP rating

IP66

Standards and approvals

MED, ABS and CCS

Dimensions

100 mm x 40 mm detector only
100 mm x 48 mm detector and base

Weight

150 g - detector only
210 g - detector and base

Materials:                         Housing

White flame-retardant polycarbonate

Sensing window

2 mm Quartz

Terminals

Nickel plated stainless steel

The Series 65 Marine Base Mounted Ultraviolet (UV) Flame 
Detector  is designed to protect indoor areas where open fires may 
be expected.

UV flame detectors are designed for use in enclosed spaces and 
require a clear line of sight within the area to be protected. They 
are unaffected by draughts or convection currents.
They are fast acting and respond to a flame more than 25 m away.

Operation

The  Series 65 Marine Base Mounted UV Flame Detector is 
sensitive to UV radiation emitted by flames during combustion. 
Since it requires only UV radiation the detector responds even to 
stationary flames with no flicker such as cigarette lighters and 
blue gas flames. 

The detector is set to respond to UV radiation (180 - 260 nm) 
emitted by almost all flames including those invisible to the naked 
eye, e.g. hydrogen fires.

The detector has a single UV sensor with a narrow spectral 
response in order to discriminate between flames and most 
spurious sources of radiation and is designed for use in internal 
fully enclosed areas.

CAUTION:

 The detector will also detect electrical 

discharges from lightning or arc welding.

Product information

Approvals

Reviews: