PSx3xxDN Instruction Manual
8
Switch configurations:
PSx30xDN, PSx31xDN-8,
PSx32xDN, PSE31xxDN
PSx31xDN-14, PSx33xDN
PSE 34xxDN
Setting the baud rate:
Up to firmware version 210:
1
2
PSx30xDN, PSx31xDN-8,
PSx32xDN, PSx31xxDN,
PSx31xDN-14, PSx33xDN,
PSx34xxDN,
OFF OFF
125 kBaud
OFF
ON
500 kBaud
250 kBaud
ON
OFF
250 kBaud
500 kBaud
ON
ON
baud rate is set via bus (default = 125 kBaud)
For firmware version 211 and higher
1
2
PSx30xDN, PSx31xDN,
PSx31xxDN, PSx32xDN,
PSx33xDN
PSx34xxDN,
OFF OFF
125 kBaud
OFF
ON
500 kBaud
250 kBaud
ON
OFF
250 kBaud
500 kBaud
ON
ON
baud rate is set via bus (default = 125 kBaud)
If the device names are given
without
the diameter of the output shaft (-8, -
14), the relevant information is valid for
all
offered output shafts (applies
throughout the document).
‘x’ in the device name stands for a number in the range 0..9. ‘xx’
in the
device name stands for a number in the range 10..999.
Important: Always replace the protective cap after setting the address.
This will prevent dust and contaminants from entering the device.
In some stainless steel variants the protective cap is not present. In this
case, device address and baud rate can only be set via bus.