AIR FILTER INSTALLATION

1.  Care should be taken to install the filters in the proper sequence. They should be installed in the following 

order: 

 

 

a) Beginning at the exhaust inlet, the first filter (Pre Filter) is the Merv 7 

 

b) Next is the filter labelled Medium Filter, Merv 14  

 

c) Followed by the filter labelled Absolute Filter, Merv 16 

2.  All filters should be installed taking note of the arrow indicating the directions of air flow and clamping into 

position. 

3.  It is important that all the filters be properly seated against the support mullion as shown in figure 4 and 5.

ECOLOAIR UNIT

FILTER SUPPORTING

FRAME

PRE FILTER

MERV 7 

AIR FLOW

(EXHAUST FILTER INLET)

MEDIUM FILTER

MERV 14 

FIGURE 4

FILTER AIR SEAL

GASKETING

CLAMP HANDLE TAPED

TO SIDE OF FILTER FOR SHIPPING

ABSOLUTE FILTER

MERV 16 

FILTER CLAMP

(PULL OUT TO LOOSEN FILTER

PUSH IN TO TIGHTEN FILTER 

AGAINST AIR SEAL)

CENTRE MULLION

ECOLOAIR UNIT

CLAMP 

HANDLE

FILTER

CLAMP

WELDED 

CLAMP

AIR FLOW

FIGURE 5

FILTER AIR SEAL

GASKETING

CLAMP HANDLE TAPED

TO SIDE OF FILTER FOR SHIPPING

ABSOLUTE FILTER

MERV 16 

FILTER CLAMP

(PULL OUT TO LOOSEN FILTER

PUSH IN TO TIGHTEN FILTER 

AGAINST AIR SEAL)

CENTRE MULLION

ECOLOAIR UNIT

CLAMP 

HANDLE

FILTER

CLAMP

WELDED 

CLAMP

AIR FLOW

Summary of Contents for EcoloAir 10000CFM

Page 1: ...URE ELECTRICAL SUPPLY CONFORMS WITH ELECTRICAL CHARACTERISTICS SHOWN ON THE RATING PLATE AND N E C REQUIREMENTS THE INSTALLATION OF THE HOOD AND DUCT WORK LEADING TO AND EXITING THE ECOLOAIR SYSTEM TO BE INSTALLED IN ACCORDANCE WITH NFPA 96 AND LOCAL CODES UL 1978 Standard for Grease Ducts UL 710 Exhaust Hoods for Commercial Cooking Equipment ULC S647 05 and or UL197 ...

Page 2: ... DETAIL LOCATED TOP OF FILTER OUTLET IF AN INLET B FAN TOP INSULATION LINING OPTION FOR EXTERIOR ICN INTERIOR FAN TOP PANEL BOTTOM FLOOR PANEL WITH TURNED UP FLANGE AT FAN INLET INTERIOR FLOOR CONNECTION FLANGE FILTER OUTLET 4 STRUCTURAL FLOOR BASE PLAN VIEW INLET PANEL CONNECTION FLANGE ACCESS SIDE INLET GASKET PROVIDED BY FACTORY FAN BOTTOM PANEL TURNED UP FLANGE FAN TOP PANEL LESS INSULATION FI...

Page 3: ...CT CONNECTIONS 1 The exhaust duct connection at the inlet entrance to the EcoloAir system must be continuously welded all around See figure 2 2 The duct must be transitioned to the full opening of the filter module inlet 3 All fan outlet openings to which ducts are attached will be provided with discharge collars See figure 3 4 All openings are to be transitioned to the duct size 5 For filter modu...

Page 4: ... the filters be properly seated against the support mullion as shown in figure 4 and 5 ECOLOAIR UNIT FILTER SUPPORTING FRAME PRE FILTER MERV 7 AIR FLOW EXHAUST FILTER INLET MEDIUM FILTER MERV 14 FIGURE 4 FILTER AIR SEAL GASKETING CLAMP HANDLE TAPED TO SIDE OF FILTER FOR SHIPPING ABSOLUTE FILTER MERV 16 FILTER CLAMP PULL OUT TO LOOSEN FILTER PUSH IN TO TIGHTEN FILTER AGAINST AIR SEAL CENTRE MULLION...

Page 5: ...d installed SCHEMATIC WIRING DIAGRAMS For field wiring diagrams and field connections refer to Halton s shop drawings shipped with unit or contact factory Additional copies of shop drawings are available on request FAN SECTION Important note Before starting the fan unit remove fan isolator hold down brackets The brackets are used for shipping purposes only When the brackets are removed the fan sho...

Page 6: ...ce charges miscellaneous tools material charges and labor charges resulting from inaccessibility of equipment will not be paid by Manufacturer This LIMITED WARRANTY SHALL APPLY ONLY to products that have been installed and maintained in accordance with the installation and Care Instruction Manuals Purchaser shall be solely responsible for adhering to the instructions and procedures set forth in th...

Reviews: