EcoloAir Operation, Maintenance & Service Manual

 

EA

OMSI/0

1

2

0

09/re

v1/EN

FILTER REPLACEMENT

To replace fi lters, proceed as follows:

 

1. Shut off fan.

 

2. Loosen the access door latches and open door.

 

3. Check how fi lters are set in place to prevent air by-pass.

 

4. Remove fi lter clamp on absolute fi lters with hook handle provided in unit, located on inside    

 

    of access door.

 

5. Remove all fi lters by sliding out the fi lter along bottom of fi lter track.

 

6. Slide the new fi lters along the bottom fi lter track and seat properly along fi lter by-pass 

 

    gasket. Replace all fi lters in this manner. Ensure all fi lters are seated properly and replace

 

    fi lter clamp to lock Absolute fi lters in place. 

 

7. Check that pressure switch air tube connection have not been disturbed by removing 

 

    pressure tube chase. 

 

8. Close access door and lock all latches.

 

9. To start fan, turn on disconnect switch at fan.

 

10. If the fan stops, remove the fi lter access door and check if all fi lters have been replaced

  

      and are seated properly. 

 

11.  Should fan continue to shut off, check all pressure switch setting

PRESSURE SWITCH ADJUSTMENTS

Check Pressure Switch Operation, proceed as follows:

 

A. Turn down Alarm Delay Timer in Ecology Control Panel. 

 

B. Turn Number 1 Pre Filter Pressure Switch down (counter clockwise), until alarm sounds and 

 

    Indicator Light illuminates (Note Setting). Return Pressure Switch to original setting

 

    (.5” Static Pressure).

 

C. Turn Number 2, Medium Filter Pressure Switch down (counter clockwise), until alarm  

 

 

    sounds and Indicator Light illuminates (Note Setting). Return Pressure Switch to original

 

    setting (1.25” Static Pressure).

 

D. Turn Number 3, High Effi ciency Filter Pressure Switch down (counter clockwise) until alarm

  

    sounds and Indicator Light on Ecology Panel illuminates. Return Pressure Switch to 

 

    original setting (2” Static Pressure). 

 

E. Turn off disconnect switch and EcoloAir Fan Section

 

F.  Turn up Alarm Delay Timer in Ecology Control Panel, set to 20 seconds.

 

G. Open Filter Access Door and remove any one Absolute fi lter. 

 

H. Turn Number 4 Overall Pressure Switch counter clockwise to lowest position on Pressure

 

    Switch Scale (0” Static Pressure).

 

I.  Ensure Filter Access Door is closed. Turn on Disconnect Switch on Ecology Fan Section.   

 

Summary of Contents for EcoloAir 10000CFM

Page 1: ... Instructions EcoloAir Unit 3000CFM 4000CFM 5000CFM 6000CFM 8000CFM 10000CFM 12000CFM 15000CFM 18000CFM 20000CFM 24000CFM 28000CFM 32000CFM 36000CFM 40000CFM UL 1978 Standard for Grease Ducts and or UL 710 Exhaust Hoods for Commercial Cooking Equipment ...

Page 2: ...aintenance Service Manual EAOMSI 012009 rev1 EN GENERAL The EcoloAir System should be installed operated and maintained as illustrated in the Installation Instruction Manual and the Operation and Maintenance Instruction 1 2 ...

Page 3: ...3 EcoloAir Operation Maintenance Service Manual EAOMSI 012009 rev1 EN MAJOR COMPONENTS FOR ECOLOAIR 1 EcoloAir Control Panel 3 Exhaust Fan Module 2 Filter Module 4 Odor Reducing Module 3 4 ...

Page 4: ...2 Pre Filter 3 Medium Filter 4 Hinged Access Door Absolute Filter 5 High Efficiency Filter 6 Ecolo Odor Reducing Module 7 Screwed On Access Panel 8 Door Latch 9 Ecolo Support Bracket 10 Fire Damper 11 Insulation 12 Hanger or Lifting Bracket 13 20 Gauge Insulation Skin 14 16 Gauge Welded Fire Proof Panels 15 Stiffner Channels 16 Removable Pressure Tube Cover 17 Pressure Tube Ports 18 Absolute Filter...

Page 5: ...2009 rev1 EN PRESSURE SWITCH AIRTUBE PARTS 1 Pressure Switch Air Tube 2 Pressure Switch Air Tube Connecting Nut 3 Elbow 4 16 Gauge Top Panel 5 Elbow Lock Nut 6 Mullion 7 16 Gauge Bottom Panel 8 Structural Base 9 Fire Proof Door Gasket 10 Filter By Pass Gasket ...

Page 6: ...n continue to shut off check all pressure switch setting PRESSURE SWITCH ADJUSTMENTS Check Pressure Switch Operation proceed as follows A Turn down Alarm Delay Timer in Ecology Control Panel B Turn Number 1 Pre Filter Pressure Switch down counter clockwise until alarm sounds and Indicator Light illuminates Note Setting Return Pressure Switch to original setting 5 Static Pressure C Turn Number 2 Me...

Page 7: ... in Step G M Reset Time Delay Timer to 50 seconds Reset Ecology Control Panel Disconnect Switch Off and On again FILTER REMOVALTEST To perform Filter Removal Test proceed as follows 1 Ensure all filters are in place and properly seated 2 Remove one absolute filter 3 Start fan Alarm should sound and fan should shut down within one minute 4 Replace High Efficiency filter 5 Restart Fan NOTE A FACTORY INS...

Page 8: ...er side of frame 3 Close the access door and lock all latches 4 Start Fan HALTON ECOLOAIR FILTER QUANTITY CHART MODEL CAPACITY PRE FILTER MEDIUM FILTER ABSOLUTE FILTER MERV 8 70 based on 3 0 to 0 10 μm MERV 14 90 based on 3 0 to 0 10 μm MERV 16 95 based on 3 0 to 0 10 μm FULL SIZE HALF SIZE FULL SIZE HALF SIZE FULL SIZE HALF SIZE 24 x 24 x 2 24 x12 x2 24 X24x15 24 x12 x15 24 x24 x12 24 x12 x12 EF3...

Page 9: ...ing A switch is provided on the Ecolo Control Panel to be activated for the desired application The unit when shipped will be set for a 20 second spray every 1 minute This can be adjusted in the field to give the required setting for each particular installation SETTING ECOLOTIME ON ANDTIME OFF CYCLE The Ecolo Unit is set to operate either 1 To set the Ecolo time on press the T ON button on the ele...

Page 10: ...18 Motor Pulley 19 Electrical Box Terminal Strip 20 Pressure Switch optional location 21 Firestat 22 Air Tubes for Pressure Switch optional location 23 Pressure Switch Box Cover optional location 24 Pressure Tube Cover optional location 25 Top Panel FANTYPES For all models a double width double inlet Class 2 airfoil type fan is used The motor and drive pack age is located in the exhaust airstream ...

Page 11: ...h the bearing collars Polishing the fan shaft with emery cloth and some light lubrication on the fan shaft will make removal much easier 4 Remove bolts fastening the bearing to the top and bottom bearing base plates 5 Re install equipment in reverse order of removal Care should be taken to properly tighten the set screws in the bearing locking collar see chart for recommended tightening torque of ...

Page 12: ...r point method with a piece of string or a straight edge The two sheaves will be aligned when two points near and far on the face of each of the sheaves touch the straight edge of the string when the string is a straight line Refer to the figure below for correct alignment Fan Sheaves Misaligned Fan Sheaves Aligned ...

Page 13: ...s run in period the belts seat themselves in the sheave grooves and the initial stretch is removed After a day or two the drive should be stopped and another check made for the correct amount of tension The tension should now compare with the values in column Normal Time If the force is below the level in column Normal Time The belts are too loose If the force is greater than the high level the be...

Page 14: ... ALARM HORN OPTIONAL RECESSED TRIM ANGLE SHIPPED LOOSE DOOR LATCH CONTROL PANEL MODELS EPLV5 1 w WASH HOODS w ECOLO EPLV5 1A w WASH HOODS EPLV5 3 w DRY HOODS w ECOLO EPLV5 3A w DRY HOOD In accordance to UL Standard S647 each filter component grease and odor shall have an interlock to prove the component is in place Where any of these interlocks are interrupted the cooking equipment shall not be abl...

Page 15: ...and reset linkage b Tighten or replace belts c Replace filters d Reset and check amperage draw e Recommend to owner to have system serviced Unit will not start a No power b Fuses blown c Off on overload heater in magnetic starter d 120 volt control transformer fuse e Blown 5 amp fuse in exhaust hood wash control panel f Defective exhaust fan motor g Fan switch on Ecology control panel in OFF positi...

Page 16: ...lter not seated properly b Broken or loose pressure switch air tube c Exhaust fan belt slipping not moving enough air d Timer not set correctly e Defective timer f Off on overload heaters g Overall pressure switch 4 not set properly a Seat filters b Repair break or tighten fitting c Tighten or replace fan belts d Set time for 60 seconds e Replace timer If burnt out it will have burn mark on top righ...

Page 17: ...tor light labeled filters overall will be illuminated and the system will shut down After the cause of the alarm has been corrected the system can be restarted by pushing the reset button and also turning the main disconnect switch to the OFF position then back to the ON position MAINTENANCE INSTRUCTIONS NOTE Heavy hamburger type operations require extra maintenance and frequent filter changes We re...

Page 18: ...ing on some fans such as arrangements 1 8 9 and 10 is often cap loaded Removal of the securing means may result in a sudden change in impeller position 5 Historical data is often the best indicator for determining the operational condition of the fan Maintenance logs which include lubrication vibration levels temperature levels power requirements inspection and other pertinent records should be ma...

Page 19: ...d and installed per drawings and in accordance with recognized acceptable engineering practices and with the fan manufacturer s recommendations 1 5 Check and tighten all bolts fasteners and set screws as necessary 1 6 Check the fan assembly and bearings for proper grounding to prevent static electricity discharge 1 7 Ensure power and drive components such as motor starter variable frequency drive ...

Page 20: ...y and recheck item 1 5 through 1 17 as the initial start up may have loosened the bolts fasteners and set screws 3 0 The fan may now be put into operation but during the first eight 8 hours of running it should be closely observed and checked for excessive vibration and noise At this time checks should also be made of motor input current and motor and bearing temperatures to ensure that they do no...

Page 21: ...e charges miscellaneous tools material charges and labor charges resulting from inaccessibility of equipment will not be paid by Manufacturer This LIMITED WARRANTY SHALL APPLY ONLY to products that have been installed and maintained in accordance with the installation and Care Instruction Manuals Purchaser shall be solely responsible for adhering to the instructions and procedures set forth in the...

Reviews: