EcoloAir Operation, Maintenance & Service Manual
EA
OMSI/0
1
2
0
09/re
v1/EN
FIRE DAMPER
The Fire Damper is located at the discharge set of the EcoloAir Filter Module. All Fire Dampers are
supplied with fusible links set to close at 286˚F (138˚C) or 165˚F U.S. Only. Should the fusible link
melt and blades shut down by gravity, linkage replacement is necessary as follows:
1. Loosen the access door latches.
2. Remove defective fusible link and replace with new link, by holding up damper blades and
wrapping link support across blades and secure at clip, on other side of frame.
3. Close the access door and lock all latches.
4. Start Fan.
HALTON ECOLOAIR FILTER QUANTITY CHART
MODEL CAPACITY
PRE FILTER
MEDIUM FILTER
ABSOLUTE FILTER
MERV 8 - 70% based on
3.0 to 0.10 μm
MERV 14 - 90 % based on
3.0 to 0.10 μm
MERV 16 - 95% based on
3.0 to 0.10 μm
FULL SIZE
HALF SIZE
FULL SIZE
HALF SIZE
FULL SIZE
HALF SIZE
24”x 24”x 2”
24”x12”x2”
24”X24x15”
24”x12”x15”
24”x24”x12”
24”x12”x12”
EF3
3000
1
1
1
1
1
1
EF4
4000
2
0
2
0
2
0
EF5
5000
2
1
2
1
2
1
EF6
6000
2
2
2
2
2
2
EF8
8000
4
0
4
0
4
0
EF10
10000
4
2
4
2
4
2
EF12
12000
6
0
6
0
6
0
EF15
15000
6
3
6
3
6
3
EF18
18000
9
0
9
0
9
0
EF20
20000
9
3
9
3
9
3
EF24
24000
12
0
12
0
12
0
EF28
28000
12
4
12
4
12
4
EF32
32000
16
0
16
0
16
0
EF36
36000
16
4
16
4
16
4
EF40
40000
20
0
20
0
20
0