CONTROL PANEL - INPUT - OUTPUT DESCRIPTION
Fire Switch – Normally Open contract of fire relay in any fire suppression system (for example Ansul) switch connected to
terminals 8 and 10
• When switch is closed, gives signal to control panel and notifies that system is on fire.
• Alarm lamp(red color)lit and display shows
FIRE
• Exhaust and Makeup fans may be shut off (depending on internal programming)
• This particular alarm remains active even when unit is in Off position
Remote AUTO/WASH/RUN switch -
Used to remotely turn the system in RUN and WASH
• If remote control for the panel is needed, this switch is on AUTO position
• This enables panel to be controlled from external or internal time clock, BMS or similar
systems.
OUTPUTS
Exhaust Fan
– terminals 1 and N.
AC voltage to energize exhaust fan starter,120 VAC.
Makeup Fan
– terminals 2 and N.
AC voltage to energize makeup fan starter,120 VAC.
Cold Water Solenoid
- terminal Q0.7 and N
Hot Water Solenoid
- terminal Q1.0 and N
Alarm signal output
– Terminal numbers to be assigned.
Dry contacts which close/open on certain alarms can be provided to send signal to remote
monitoring system.