25
Capture Jet
®
Water Wash
Operation & Maintenance & Service Manual
CJ
O
WWM/0
120
09/re
v1/EN
OPERATING MODES - SEQUENCE OF OPERATION
OFF MODE
• The unit displays
WASH DONE STAND BY
• All outputs are off
• Indicator light “System OK” is lit. System is ready to be started again.
• Statistics can be consulted/cleared using appropriate keys
RUN MODE
• Put selector switch ”RUN/WASH” in RUN position
• The unit displays
SYSTEM ON FAN ON
first row
• The unit displays
COLD WATER MIST ON
second row (if applicable, for HC5-25)
• Exhaust fan is on
• Make up air fan is on
• Cold water solenoid on
• Statistics can be consulted/cleared using appropriate keys
WASH MODE
• Select RUN/WASH switch in WASH position-turn off sequence is as follows:
• The unit displays
WASH ON 60 SEC DELAY
• Exhaust fan is off
• Make up air fan is off
• Washing cycle is delayed for 60 seconds allowance for fan to stop.
Automatically after 60 seconds of delay panel is going to washing cycle :
• The unit displays
WASH ON_____MIN
• The display is showing the current time on washing hoods.
• The hot water solenoid is on
• Detergent pump is on
• Washing cycle finishes after preset time ( by default 3 min)-this is adjustable by wash
time setting button
After the first wash cycle finishes by program the system automatically shuts down in stand by. If the panel has
more than 1 sequence 2,3 and 4 will start automatically once the previous sequence is completed.
• The hot water solenoid is on
• The unit displays
WASH DONE STAND BY
This message will persist until operator put the selector switch in RUN.