M.A.R.V.E.L.  Installation Operation & Maintenance Manual

 

MAR

VELIO&M/0220

09/re

v1/EN

Equipment

 

Description

Power + Connection Details

PT

 

Hood plenum 
pressure 
sensor

Used to calculate air fl ow in a hood in real time.

• 

Power source:

 24 V DC power 

supply located in a control panel.

 

Connection:

 at terminal block 

located behind a cover on the 
Capture Jet

®

 plenum.

ABD

Automatic 
balancing 
damper

NOTE:

 For multiple hood installations with a single 

exhaust fan only

Adjusts air fl ow with motorized balancing 

• 

dampers attached to a collar at each hood. 
Damper controlled by a 0-10 V DC position 

• 

reference signal generated by a controller.
Upon power failure, the automatic balancing 

• 

damper fully opens. 

Power source:

 24 V AC 

transformer located in the control 
panel. 

Connection:

 at terminal block 

located behind a cover on the 
Capture Jet® plenum

Alarm light and 
audible alarm/ 
buzzer

Activated when any alarm condition is detected. 

• 

Common alarm conditions include: fi lter missing, 

• 

fi lter clogged, fi re suppression system activated, 
duct temperature dangerously high, sensor 
failed, or VFD is in fault. 

NOTE: 

To easily diagnose the alarm, use the remote 

Konsole™ Diagnostic Software.  

Override push 
button

Used to override pre programmed operation.

• 

Two modes:

• 

Press and hold for 1 second to accelerate 

1. 

the exhaust rate to 100% of the design air 
fl ow for a pre programmed period of time 
(default 5 minutes.)  
Press and hold for 3 seconds to accelerate 

2. 

the exhaust rate to 100% of the design air 
fl ow for a pre programmed period of time 
(default 1 hour.) Starts the hood if it has 
been overridden by a schedule or an ‘off’ 
state.

Connection:

 at terminal block 

located behind a cover on the 
Capture Jet

®

 plenum.

Room 
temperature 
sensor

Mounted on a kitchen wall close to a thermostat.

• 

Connections:

 to the control panel 

with 2 wires

VFD

Variable 
Frequency 
Drive 

Controls the speed of a three-phase fan motor 

• 

by changing the frequency of the current to the 
motor.
For smaller fans, mount the VFD in a cabinet 

• 

attached to a hood. 
For larger exhaust fan units, attach the VFDs to a 

• 

fan unit or cabinet or mount remotely.

Power source:

 varies as per fan’s 

voltage requirement

Connection:

 at terminal block in 

VFD control panel to main control 
panel

Speed reference:

 0-10 VDC

Summary of Contents for M.A.R.V.E.L.

Page 1: ...M A R V E L Model based Automated Regulation of Ventilation Exhaust Levels Operators Manual Installation Operations and Maintenance Instructions PT...

Page 2: ...al control panel for multiple units with a single fan 13 6 Check pressure transducer 13 7 Calibrate and align IRIS Sensor 14 9 Calibrate the Capture Jet and exhaust air ows 14 10 Calibrate M A R V E L...

Page 3: ...w adjustment depending on cooking activities Control of common exhaust fan for minimum energy consumption at all times Automatic or on schedule start stops Automatic balancing dampers Early re warning...

Page 4: ...emperature sensor to measure changes in cooking status Example Differential Pressure Transducer Used in conjunction with the value from the temperature sensor and IR Index to measure and control the a...

Page 5: ...E L System Components Overview A key feature of the M A R V E L system is exibility It can be applied to a single hood or over multiple hoods depending on the requirements FLOW AIR TS FUSIBLE LINK IR1...

Page 6: ...it is necessary to start the hood fan in idle mode Used to measure a rapid change in temperature of cooking surfaces for example cooking activities and adjust the air ow in the hood to the required l...

Page 7: ...temperature dangerously high sensor failed or VFD is in fault NOTE To easily diagnose the alarm use the remote Konsole Diagnostic Software Override push button Used to override pre programmed operatio...

Page 8: ...rol panel see below is also required Provides permanent Ethernet connection optional Provides temporary Ethernet connection for service Provides RS232 cable connection for on site service Power source...

Page 9: ...tivity sensed from IRIS sensor s Minimal exhaust ow captures any appliance generated heat Default is 60 of design air ow or as adjusted to meet requirements After idle mode enters Active mode Active M...

Page 10: ...trol System continuously monitors exhaust air ow at each hood and generates a signal 0 to 10 V proportional to total exhaust air ow as fraction of total design 0 V system is off 7 V system operates at...

Page 11: ...0 442 5866 or 1 800 4 HALTON If a problem cannot be correct through verbal or written communication with Halton support the system can be connected to the Internet for remote access to Halton engineer...

Page 12: ...r details 2 Make central control panel connections for multiple units with a single fan Make the following connections at the central control panel a 120 VAC 5 amp power to control panel b Space tempe...

Page 13: ...e provided by Halton connect each unit to the central control panel This includes Attach the wire to the terminal block in the control panel mounted on the hood 1 Run the wire to the central control p...

Page 14: ...distance between the sensor and the tool should guarantee the eld of view of the sensor will be completely within the black body surface 5 Register the space temperature t in F 6 Register the IR _Temp...

Page 15: ...ly 10 Calibrate M A R V E L System for multiple units with a single fan NOTE Make sure that the lters are in place prior to calibration To calibrate the M A R V E L system follow these steps 1 Open th...

Page 16: ...een Select the Process tab 5 When the calibration is completed con rm that there is a value 0 in the Calibrated_ SP eld NOTE If calibration must be aborted select the Reset_Calibration eld When ready...

Page 17: ...rature IRT and exhaust air temperature Tex for each hood Calculate and report hood exhaust airflow Q to the exhaust fan controller IRT Tspace dTcook Tex Tex_min Maintain hood exhaust airflow Q Qdesign...

Page 18: ...plenum door to allow an air jet to protect the sensor optics from contaminants However periodic cleaning may be required to keep the optics clear Gently clean the IRIS socket with isopropyl alcohol o...

Page 19: ...am for the correct terminations points Remove the face plate of the sensor by removing the 4 face plate screws 2 Lift out the face plate and sensor and gently pull out the sensor wires 3 Remove the se...

Page 20: ...sconnect the temperature sensor from the terminal block located in the Capture 1 Jet hood Refer to the terminal block diagram on the Halton supplied wiring diagram for the correct terminations points...

Page 21: ...und the 1 perimeter Remove the actuator cover by removing the 1 screw on the side 2 Disconnect the power to the actuator 3 Record the DIP switch values located in the red holder on the bottom of the a...

Page 22: ...eplacement actuator Halton Part 16012 Tighten the U bolt on the 7 drive shaft Reset the DIP switches 8 Reset the stop screws 9 Reconnect the power 10 Calibrate the new actuator by pressing the 11 Rese...

Page 23: ...housing and the exterior metal cover as before 12 Balancing Damper Actuator Removal Replacement To remove the pressure transducer follow these steps Turn off power to transducer 1 Remove covering on p...

Page 24: ...ove pressure transducer faceplate 4 screws 5 Remove side mount screws 2 screws 6 Replace with Halton Part 18028 7 Reconnect wires and tubing as before Check that the tubing is not kinked 8 5 Remove fa...

Page 25: ...connection for startup troubleshooting by Halton Technical Support only Temporary cable to laptop connection as required for support RS232 cable connection to laptop pre loaded with KONSOLE software f...

Page 26: ...59 80 F Appliance ON 80 F Power supply off 220 F NOTE if more than 1 IRIS sensor check each IR_Index value If all values are 220 check that power supply Duct_DP Exhaust fan OFF 0 00 IWC Exhaust fan ON...

Page 27: ...on CE Alignment Tool does not work Battery low Replace battery Unscrew end of tool remove the battery and replace with same type Exhaust damper blades do not open or close Loose set screws Tighten In...

Page 28: ...ted with a should be kept readily on hand the amount depending on the number of hoods in the system NOTE Contact Halton for information on other replacement parts as required Part Halton Part Number P...

Page 29: ...d States Halton Company 101 Industrial Drive Scottsville Kentucky 42164 www haltoncompany com Tel 270 237 5600 Toll Free 800 442 5866 Fax 270 237 5700 Canada Halton Indoor Climate Systems 1021 Brevik...

Page 30: ...charges miscellaneous tools material charges and labor charges resulting from inaccessibility of equipment will not be paid by Manufacturer This LIMITED WARRANTY SHALL APPLY ONLY to products that hav...

Reviews: