background image

INSTALLATION OF THE BURNER DOOR DURING SERVICING

34000 Autry Street, Livonia, MI 48150 • 800.968.5530 • Fax 734.419.0209 • www.hamiltonengineering.com • LIT91178 REV 5/2017

Page 8 of 9

Proper precautions must be taken when installing the EVO burner door. Faulty installation or using a door
in need of replacement risks leakage of combustion products, or further, a damaged heat exchanger that
will not be covered under warranty.

Any time the burner door is removed, it should be thoroughly inspected before being put back into

service. There are two gaskets on the burner door; the first is the inner rope gasket, which is permanently

affixed to the burner door. If this gasket is completely compressed (having no sealing ability), the door

must be replaced. The second gasket is on the perimeter and is made of rubber; this gasket is easily

replaced and comes as a standard part of the maintenance kit (and should always be replaced during the

annual maintenance procedure). To limit risks, the following instructions must be adhered to.

PROPER PROCEDURE

Before installing a burner door, the two gaskets and the burner door refractory must to be checked for damage or 

deterioration and proper placement (rubber gasket and refractory); once this inspection is completed, the burner door can 

be mounted with the six M6 nuts. 

Please note: Over-tightening the M6 nuts may cause the threaded rods on the 

front of the heat exchanger to break!

 If excess resistance is encountered when installing an M6 nut, discard that nut 

and use one of the spares shipped with the unit.

The maximum torque for assembling a burner door nut is 3.7 ft-lb or 44.4 in-lb

Use a torque wrench suitable for this torque range, to tighten the nuts.

M6 nuts and thread studs

 

After starting up the unit:

To limit the risk of leaking combustion products, a leak test of the burner door gaskets with a hand held 

combustion gas leak detector (sniffer) must be done.

See next page for detailed photos of burner door and gasket conditions.

Summary of Contents for EVO 299

Page 1: ...ld result in loss of warranty and or severe personal injury death and or substantial property damage 34000 Autry Street Livonia MI 48150 800 968 5530 Fax 734 419 0209 www hamiltonengineering com LIT91...

Page 2: ...the owner An inspection should cover at a minimum the following areas Download and review operating hour data and fault history Inspect all fittings controls and connections for leaks damage or fouli...

Page 3: ...e front of the heat exchanger to break If excess resistance is encountered when installing a M6 nut discard that nut and use one of the spares shipped with the unit The maximum torque for assembling a...

Page 4: ...te cleaning instructions on page 53 55 Check the distance from the electrode to the burner there should be a 3 8 gap in between the two If the existing electrode pins must be adjusted for proper gap c...

Page 5: ...PRESSURE P MODEL AIR PRESSURE P HW129 6 wc HW399 1 wc HW179 96 wc HW599 86 wc HW199 1 68 wc HWH 1499 1999 8 wc Hamilton EVO Products Flow and Pressure Drop GPM Feet of Head Design HW 79 129 8 HW 179 1...

Page 6: ...at high fire Water temperature 160 180 F gives the hottest flue gasses All readings must be taken with boiler front cover installed Doing the measurements under these conditions will give the most acc...

Page 7: ...e sure the bucket is under the open drain trap assembly to catch the debris and water 4 Rinse out the clean out cap in a sink to remove any dirt or buildup that may have accumulated 5 Condensate drain...

Page 8: ...t and should always be replaced during the annual maintenance procedure To limit risks the following instructions must be adhered to PROPER PROCEDURE Before installing a burner door the two gaskets an...

Page 9: ...ering com LIT91178 REV 5 2017 Page 9 of 9 INSTALLATION OF THE BURNER DOOR DURING SERVICING New Burner Door Rope gasket in good condition Rope gasket raised above door surface good Damaged Burner Door...

Reviews: