background image

Hamilton

 

Home

 

Products

                          

Canal

 

Winchester,

 

OH

 

76106

                        

61MH0028A

                                

Page

 

8

 

SECTION VI: UPFLOW CONFIGURATION 

This kit is approved for use in an alcove or closet installations 
with an approved air conditioning coil. The upflow coil 
cabinets are available in a 28” and 36” height. The upflow 
configuration requires either a 20” tall return air cabinet or a 
24” tall return air cabinet under the coil cabinet making the 
total height of the furnace, coil cabinet and return air cabinet 
heights 81” or 93”. To install the coil cabinet assembly and the 
return air assembly follow the steps below. 

 

Prior to installing the furnace make sure the holes are cut into 
the floor for the refrigerant tubing, the drain line, the line 
voltage supply wiring, the thermostat wiring and the 
condenser control wiring. 
1.

 

Before installing the coil cabinet on the furnace, be sure 
you have enough clearance to install the furnace, the coil 
cabinet and the return air cabinet. 

2.

 

Remove the top shipping cover and corner posts. 

3.

 

Remove the bottom shipping cover. 

4.

 

Remove the front access panel (door). 

5.

 

Remove the coil cabinet from the shipping box. 

6.

 

Place the coil cabinet on top of the furnace and secure 
with screws. 

7.

 

Turn the furnace and coil cabinet upside down to put the 
furnace and coil cabinet in the up-flow position. 

8.

 

Place the return air cabinet at the bottom of the coil 
cabinet. Use the screws provided in the kit to secure the 
return air cabinet to the coil cabinet. 

9.

 

Slide it into position on the supply air duct connector. Use 
the duct collar to secure the supply air duct to the top of 
the furnace. Be careful when installing the duct collar not 
to use pointed screws in the control box and make sure no 
screws are touching any components or wires. 

10.

 

Place the cooling coil into the coil cabinet. Follow the 
instructions provided with the outdoor cooling unit and 
the evaporator coil to properly connect the refrigerant 
piping to the evaporator coil and the drain lines to the 
condensate drain pan. Make sure the coil and drain pan 
are all the way to the back in the cabinet so the hole in the 
center of the drain pan lines up with the hole in the center 
of the coil cabinet. 

11.

 

Place the cooling cabinet front door on the unit by 
inserting the tabs in the bottom of the door into the slots 
in the coil shelf, line up the strike in the front flange of the 
top cover and push the two strikes into the both latches on 
the front flange on the door. 

 

NOTE: The installer must provide a strap that attaches to 
the top of the furnace and is secured to the alcove or 
closet wood framing 

 

12.

 

The 24” tall return air cabinet requires two standard 16” x 
16” x 1” and one 24” x 24” x 1 disposable air filters in the 
filter tracks located inside the return air cabinet. 

13.

 

The 20” tall return air cabinet requires two standard 18” x 
18” x 1” and one 18” x 20” 1” disposable air filters in the 
filter tracks located inside the return air cabinet. 

14.

 

Install a louvered grille in the front of the return air 
cabinet. 

 

Figure 12: Typical Upflow Installation 

 

SECTION VII: LINE VOLTAGE WIRING 

 

Power Supply 

The furnace internal wiring is complete except for the power 
supply and the thermostat wires. See wiring diagram and/or 
Tables 6 and 7 for wire size, fuse/circuit breaker size, and 
ground wire sizes. The use of cable connectors on incoming 
power supply wires to relieve any strain on wiring is 
recommended. Follow the steps below to connect the power 
supply wires. 

 

Single Circuit Line Wiring Connections

 

1.

 

Remove the control box cover. 

2.

 

Install the cable connectors on the 7/8” dia holes on the 
right side of the control box. 

3.

 

Strip ½” of the insulation on the end of each wire. 

4.

 

Insert the wires through the holes in the casing and 
through the cable connectors. 

5.

 

Insert the black wire into the L1 screw terminal on the 
first circuit breaker from the top and tighten the set screw 
to clamp down on the wire. 

6.

 

Insert the white or red wire into the L2 screw terminal on 
the first circuit breaker down from the top and tighten the 
set screw to clamp down on the wire. 

7.

 

If you are using a single circuit for a 12kW, 15kW or 
20kW model you will need to install a black jumper wire 
from the L1 terminal on circuit breaker #1 to the L1 
terminal on circuit breaker #2 and a white or red jumper 
wire from the L2 terminal on circuit breaker #1 to the L2 
terminal on circuit breaker #2. Refer to Figure 14 for 
circuit breaker locations.  
Note: The 100-amp 4 Pole Jumper Bar Assembly part 
number 68BAE001 can be used in place of the jumper 
wires. 

Summary of Contents for WE30 Series

Page 1: ...er Location 11 29 Wiring Diagram 20 kW w C T Blower Motor 22 15 Control Box Power Low Voltage Wire Locations 13 LIST OF TABLES 1 Electric Furnace Model Specifications 2 8 Electrical Data 10 2 Model No...

Page 2: ...Single Stage Heating 30 Table 2 Furnace Model Nomenclature Coil Cabinet Model Front Door of Cabinet Open Top 17 3 4 x 21 3 4 Maximum Air Flow CFM 1 Pleated Air Filter In The Door 2 Pleated Air Filter...

Page 3: ...ce heating cooling equipment Untrained service personnel can perform basic maintenance functions such as cleaning of exterior surfaces and replacing the air filters Observe all precautions in the manu...

Page 4: ...y a closet or alcove must have a certain total free area opening for the return air For A C and HP Furnaces 1 3 HP Blower Minimum 200 in free area opening Use Return Grille or Coil Cabinet For A C and...

Page 5: ...to use SECTION IV SUPPLY AIR AND DUCT CONNECTOR INSTALLATION Duct Connectors 90 DCU0 XX Duct Connectors The duct connector is used to provide a sealed connection between the furnace base and a under...

Page 6: ...the insulation around the perimeter of the duct connector opening 5 Install the floor base over the floor opening with the flanges on the 11 x 13 inch opening facing down Refer to Figures 8 and 9 6 Lo...

Page 7: ...to the floor by drilling two holes through the furnace base and the floor base at the right and left front inside corners of the cabinet Use two screws to secure the furnace to the floor Figure 10 Re...

Page 8: ...e coil cabinet 11 Place the cooling cabinet front door on the unit by inserting the tabs in the bottom of the door into the slots in the coil shelf line up the strike in the front flange of the top co...

Page 9: ...Electrical Code Part I CSA C22 1 and local codes for additional requirements concerning supply circuit wiring Electrical data can be found in Tables 6 7 and 8 IMPORTANT All installation on field wiri...

Page 10: ...er supply will require circuit breaker jumper bar or a jumper wire Refer to the National Electrical Code Table 250 95 for Non Sheathed Conductor Ground Wire Ground conductor must be the same size and...

Page 11: ...le codes Figure 14 Control Box Cover and Circuit Breaker Location Dual Element Box For personal safety be sure to turn the electrical power OFF at the main circuit panel Home Circuit Breaker Box and a...

Page 12: ...cated on the blower housing 6 Follow the instructions in the USERS INFORMATION MANUAL to properly start up the air handler POWER SUPPLY CONNECTIONS If the air handler has been installed prior to insta...

Page 13: ...Installation The thermostat heat anticipator must be set at 0 7 Amps if the thermostat has a manual heat anticipator adjustment This setting should be checked at the time of installation The thermost...

Page 14: ...R Figure 16 Separate Thermostats Separate Air handler and Cooling Unit G R W R G Y Heating Thermostat Cooling Thermostat C Y R G W C COM HEAT COOL Thermostat Interlock Switch Air Handler 24 VAC Transf...

Page 15: ...8 strain relief in the control box and place the thermostat wire cable next to the low voltage terminal block 6 Connect the Red 24 VAC supply thermostat wire to the red pigtail wire and secure the two...

Page 16: ...peratureSwitch W2 J u m p e r Figure 22 Typical Heat Pump 2 Stage Heating Cooling Connections SECTION X MOTOR BLOWER AND FURNACE START UP Selecting the Constant Torque Blower Speed This furnace uses t...

Page 17: ...s to the furnace at the main circuit panel House Circuit Breaker 14 Set the thermostat to the desired temperature Figure 24 Blower Assembly and Blower Deck SECTION XI FINAL SYSTEM CHECKOUT 1 Refer to...

Page 18: ...BLK W H T G R N Y E L L2 B L K WHT B LU B L K BM G R N GGS Y E L C L A S S 2 CLASS 2 CC COMPRESSOR CONTACTOR RVS REVERSING VALVE SOLENOID LEGEND TB TERMINAL BLOCK BMFP 6 PIN MOLEX BLOWER MOTOR PLUG A...

Page 19: ...L1 HC1 T2 L2 G R N GGS C L A S S 2 WHT W H T WHT CLASS 2 CC COMPRESSOR CONTACTOR RVS REVERSING VALVE SOLENOID LEGEND TR TRANSFORMER BMFP 6 PIN MOLEX BLOWER MOTOR PLUG ASSEMBLY GND GROUND CONNECTION B...

Page 20: ...N B R N BRN BLK WHT BLK BLK THERMOSTAT W2 BLK BLK BLK BLK B L K B L K B R N BRN B R N BRN B R N HPM 7 RED ST1 8 BLK L1 9 BLU ST4 Y E L L 2 G R N G N D P R P S T 3 B L K S T 5 B R N 2 4 V C O M BRN G N...

Page 21: ...40 VAC 24 VAC BLK 1 BLK SUPPLY WIRING XMC0 402EBBC Contactor L1 T1 L2 T2 HC1 BLU BLU L1 GND G BLK WHT G R N R E D HC1 HTR1 BLK BLU RED RED T1 C B L1 C irc u it 1 L2 C B C irc u it 1 B L K HC1 T2 L2 1...

Page 22: ...BRN BLU GND BLU PRR ST3 ORN ST2 B R N 2 4 V C O M B L U S T 4 O R N S T 2 P R P S T 3 B L U O R N P U R B L U B L U W H T W B R N BLU B L U B L K B L K R E D R E D FOR A TWO STAGE HEATING THERMOSTAT R...

Reviews: