SECTION VIII: FIELD INSTALLED ELECTRIC
HEATER KITS
This instruction covers the physical installation of the following
electric heat kits on the WE30 series models. Refer to Tables 6-
8 for electrical specifications.
Model No.
Voltage
Phase
Hertz
Heater kW
BE30HK-10A
208-240
1
60
10
BE30HK-12A
208-240
1
60
12
BE30HK-15A
208-240
1
60
15
BE30HK-20A
208-240
1
60
20
Field Installed Electric Heat Kit
Table 9: Field Installed Electric Heater Kit Model
Numbers.
The field installed electric heat accessories are used on cooling
or heat pump models that were not purchased with electric heat
from the factory. Each air handler model is approved for use
with the field installed accessory electric heat kit.
INSTALLING THE HEATERS
1.
Follow the instructions in the USERS INFORMATION
MANUAL to properly shut down the air handler.
2.
Remove the block off plate that covers the heater openings
and discard. Retain the screws; they will be used to secure
the electric heater mount plate.
3.
Insert electric heat kit into the opening where the block off
plate was removed. Secure the mounting plate with the
screws that were removed from the block off plate.
4.
Connect the six-pin male plug on the electric heater
assembly to the six-pin female plug mounted on the side of
the low voltage control box divider panel.
5.
Remove the wiring diagram from the kit, remove the paper
that covers the adhesive back and place the electric heat
wiring diagram over the wiring diagram located on the
blower housing.
6.
Follow the instructions in the USERS INFORMATION
MANUAL to properly start up the air handler.
POWER SUPPLY CONNECTIONS
If the air handler has been installed prior to installing the electric
heaters or if an older unit is being replaced, the supply power
wires must be checked to make sure the wires are the proper
sizes to handle the current load for the heaters Refer to Tables 6-
8 for correct wire size. If the supply power wire size is incorrect,
new wires will need to be installed. Follow the instructions
“Power Supply Wiring” on page 8 of these instructions for
proper installation.
For circuit breaker models only -
After the supply wiring has
been connected to the circuit breakers you must remove the
transformer and indoor blower motor wires from the terminal
block and connect them to load side of circuit breaker #1.
LOW VOLTAGE CONNECTIONS
If the air handler was previously installed, nothing will need to
change on the low voltage wiring. If this is a new installation
refer to SECTION VII on page 12 of these instructions.
Series
Type
Accessory
Heating Capacity
@ 240 VAC, 1 PH
Revision
B = Breaker
E30 = MH
Electric Heat
Models
HK = Heat Kit
A
06 = 6 kW
08 = 8 kW
10 = 10 kW
12 = 12 kW
15 = 15 kW
20 = 20 kW
Table 10: Field Installed Electric Heater Kit Nomenclature
To prevent damage, carefully insert the electric heating
assembly through the rectangular opening in the front of the
discharge opening so the heat element support rod is seated
into the hole on the back side of the discharge opening.
After installing the electric heater, a one-inch clearance
must be maintained on all sides of the supply air duct
and/or plenum for a minimum of thirty-six inches from the
air handler discharge opening.