HAMWORTHY HEATING LTD
31
PUREWELL
Vari
Heat c
500001169/T
8.2.6 - Parameter settings for the Enduser
The boiler is supplied with default settings. These must be modified to suit individual Enduser needs.
Press one of the line selection buttons.
This will take you to programming level <<Enduser>>
Press the line selection button to choose the relevant line.
The display shows <<Pxxx>>
Adjust the required value with one of these buttons. The adjustment is stored as
soon as you change to some other line (to alter individual items, a change of
parameter is required).
The Enduser Parameter list details all possible settings.
Press button to leave the programming level.
Changes will not be stored
Press the Info button to leave the programming level.
Changes will be stored
Note:
If no button is pressed for about 8 minutes, the screen will automatically return to the default
display. Changes will not be stored. When switching to another level, changes will be stored.
Figure 8.2.6 - Overview of Enduser parameters
Line
Function
Range
Unit
Resolution
Default value
Time of day
1
Time of day
0...23:59
h / min
1 min
---
Setpoints
5
Reduced room temperature setpoint «TrSollRed» or
(reduced boiler temperature setpoint «TvSollRed»)
(When using an additional room unit, line 5 will be hidden)
TRF...TRN
°C
0.5
16.0
Time program HK1 (heating circuit 1)
11
Time program HC1 switch-on time 1
st
period
00:00...24:00
hh:mm
10 min
06:00
12
Time program HC1 switch-off time 1
st
period
00:00...24:00
hh:mm
10 min
22:00
13
Time program HC1 switch-on time 2
nd
period
00:00...24:00
hh:mm
10 min
24:00
14
Time program HC1 switch-off time 2
nd
period
00:00...24:00
hh:mm
10 min
24:00
15
Time program HC1 switch-on time 3
rd
period
00:00...24:00
hh:mm
10 min
24:00
16
Time program HC1 switch-off time 3
rd
period
00:00...24:00
hh:mm
10 min
24:00
8.2.7 - Start-up / Initialisation
On startup after power-On, or after a lockout reset, the setpoints will be initialized.
These setpoints apply until a first adjustment is made (e.g. via the screen display or PC parameterization):
After a readjustment, these values will be overwritten with the new value and permanently stored in the LMU.
When a new startup is made, or after power-On, the previous settings will be stored in the LMU.
Also, the software version number of the operator module and that of the connected type of LMU... will be deliv-
ered.
Summary of Contents for Purewell VariHeat 70c
Page 2: ......
Page 43: ...HAMWORTHY HEATING LTD 37 PUREWELL VariHeat c 500001169 T Figure 8 3 11 Operating phases ...
Page 44: ...HAMWORTHY HEATING LTD 38 PUREWELL VariHeat c 500001169 T Figure 9 0 Boiler Wiring Schematic ...
Page 65: ...HAMWORTHY HEATING LTD 59 PUREWELL VariHeat c 500001169 T Figure E1 2 Typical Piping Layouts ...
Page 70: ...HAMWORTHY HEATING LTD 64 PUREWELL VariHeat c 500001169 T NOTES ...
Page 71: ......