background image

 
HAMWORTHY HEATING LTD 

25 

SPETISBURY 

 

500001118/C 

13.0   SERVICING  &  MAINTENANCE 
 

A qualified engineer registered for working on non 
domestic gas or oil appliances should check and ensure 
that the flue, its support and terminal, the ventilation to 
the boiler house, safety valve, drain, water filter if fitted, 
pressure gauge, etc.; are in a serviceable and working 
condition and still comply with the relevant standards 
and codes of practice - see 

Section 3.1 

 
The boiler should be serviced at regular intervals, 
not exceeding TWELVE months. In the case of 
continuous operation, the maintenance operations 
should be carried out every SIX months. 
 

When carrying out boiler servicing always 
consider both your own safety and that of 
others.  The use of protective equipment (e.g. 
eye protection, face mask, protective gloves, 
etc.) is recommended where necessary. 

 

13.1    Initial Inspection 
 
a.

  Operate boiler and check for any signs of 

unsatisfactory operation, water leaks, gas leaks or 
unusual noise from burner. 

b.

  After allowing burner to reach stable firing 

conditions for approximately 15 minutes, carry out 
combustion gas check. 
Measure CO

2

, CO, flue gas temperature and water 

temperature rise across the boiler.  The readings 
obtained should be noted for reference upon 
completion of the servicing procedure. 

c.

   Measure gas pressure at inlet to burner gas 

train. 

d.

  Check operation of both boiler and heating 

system controls, then set burner  to OFF. 
Allow the boiler/burner to cool. 
 

13.2    Burner Service Procedure. 
 
SWITCH OFF ELECTRICAL SUPPLY AND FUEL 
SUPPLY TO BOILER. 
 

a.    Disconnect electrical and fuel connections to 
burner. 
b.

Disconnect burner from mounting flange and 

remove from front of boiler (taking care to remove 
thermostat bulbs). 
c.

Check the burner head for any signs of 

damage or degrading of the material. Cleaning 
should only be done using a soft bristle brush and 
vacuum cleaner. 
d.

Examine the condition of the electrodes and 

check that they are clean, undamaged, and not 
loose. If necessary, remove, clean using a very fine 
emery paper and then refit. For the correct spark 
gap and position of the electrodes, refer to Fig. 11.2 
In this manual. 
e.

Examine all gasket material and check for any 

signs of damage or degrading. If necessary, replace 
them, but always use the correct type. 
f.

Check all electrical connections and cables to 

ensure that they are all sound, undamaged and 

have not worked loose. 
g.

Remove and clean the flexible tube to the air 

pressure switch and check that this is functioning 
correctly. 
h.

If required, clean the combustion air fan. 

i.

Refit all parts and reconnect the electricity 

and gas supplies. 
j.

Check for gas soundness and electrical safety 

before switching on. 
k.

Switch on the burner and check for correct 

operation. 
l.

Check combustion CO and CO

2

, levels at 

both the minimum and maximum fan speeds as 
described in Section 10.6 and adjust if necessary. 
 

IF IT IS NECESSARY TO REPLACE ANY PARTS, 
REFER TO SECTION 14.2 OF THIS MANUAL FOR 
CORRECT PART NUMBERS. 
 
13.3      Boiler Service Procedure 
 
a

.          After removing burner, remove boiler casing 

and front insulation to gain access to front section of 
boiler.

 

b

.          Remove heat exchanger access plates (11, 

12  and 15 referring to Fig. 14.1), and corresponding 
insulation panels, from boiler front section. 
Boiler combustion chamber and heat exchanger 
flueways are now accessible for cleaning with 
suitable brushes and a vacuum cleaner. 

c

.          Access  to  rear  of  heat  exchanger  flueways 

and combustion chamber can be obtained by 
removing rear insulation wrap, flue box (Fig. 14.1 
item 31), cover plate (Fig 14.1 item 32), insulation 
and fire brick (Fig. 14.1 item 28) from rear of boiler. 
The refractory fire brick (Fig. 14.1 item 28), located 
at the rear of the boiler, should be checked at least 
once every two years and replaced if necessary. 

N.B.

  Removal of flue box requires disconnection of 

flue. 

d

.          Replace  all  access/cover  plates,  ensuring 

that all gaskets and insulation panels are correctly 
fitted. 
Refit securing studs/nuts and tighten evenly. 

e

.          Refit  boiler  insulation  and  casing.  For 

guidance, refer to 

Section 10.

 

f

.           Refit  burner.    Reconnect  fuel  and  electrical 

supplies. Refit and ensure thermostat bulbs are 
correctly located in pocket. 

g

.          Turn on fuel supply and check soundness of 

fuel supply pipework. 

h

.          Check all flue joints for integrity. 

i

.           Check ventilation ducts/grilles to boiler room 

and ensure they are clear. 

j

.           Re-commission boiler as detailed in relevant 

parts of 

Section 11.0: COMMISSIONING & TESTING 

Summary of Contents for Spetisbury

Page 1: ...MUST BE READ AND UNDERSTOOD BEFORE INSTALLING COMMISSIONING OPERATING OR SERVICING EQUIPMENT Spetisbury Boilers Gas Fired Cast Iron Sectional Boilers 110kW to 340kW Installation Commissioning and Serv...

Page 2: ...ating safely and efficiently Maintenance Agreements 01202 662555 Regular routine servicing of equipment by Hamworthy service engineers inspects the safety and integrity of the plant reducing the risk...

Page 3: ...ON GROUP H NATURAL GAS 2ND FAMILY I2H PLEASE ENSURE RELEVANT INFORMATION REQUIRED WITHIN DOCUMENT IS FOUND RELATING TO SPECIFIC FUEL TO BE FIRED BEFORE FIRING BOILER THIS BOILER COMPLIES WITH ALL REL...

Page 4: ...aste Gas Volume and Temperature 6 3 Materials 6 4 Suction 6 5 Disconnection 6 6 Flue Discharge 6 7 Surface Temperatures 6 8 Flue System Location 6 9 Condensate Discharge 7 0 AIR SUPPLY 6 7 1 Air Suppl...

Page 5: ...nd Vent Pipe Sizes 7 Figure 9 1 Electrical Wiring Diagram 8 Figure 10 1 Composition of Sections Within Heat Exchanger 9 Figure 10 2 Boiler Section Identification 10 Figure 10 3 Rear Section and Cradle...

Page 6: ...nstallation Typical 30 Figure 15 2 Dimensions and Clearances 31 Figure 15 3 Burner Clearances 31 Figure 15 4 Stacked Boiler Dimension 32 Figure 15 5 Burner Mounting Plates Dimensions SP 110 150 220 33...

Page 7: ...er The section to section flue gas seal is made by d A mastic strip around the outer perimeter of each section e A mastic strip around the perimeter of the combustion chamber of each section The secti...

Page 8: ...box f Burner mounting plate drilled ready to accept burner SP 110 150 220 only Burner mounting plate not required on SP 280 or 340 g Steel cradle Remove all the packing material and inspect the equip...

Page 9: ...uidance note PM5 Automatically controlled steam and hot water boilers CIBSE Publications CIBSE Guide It is impractical in this document to specify all relevant information but the following extracts f...

Page 10: ...weight of the boiler including pipework and ancillary equipment when filled with water A steel sheet can be placed beneath the boiler cradle to facilitate movement of the boiler during assembly If a...

Page 11: ...s not connected to a chimney system but is connected directly to outside by a standard stainless steel flue either single or twin wall it is particularly important to ensure that the point at which it...

Page 12: ...d except by a design which when closed for maintenance the boiler is open to atmosphere The pipe shall be protected against freezing where this might occur 8 4 Altitude Gauge Water Pressure Gauge Ever...

Page 13: ...information contact Hamworthy Heating for details 8 5 Thermometer See Figure 15 1 for typical position A thermometer complete with pocket should be fitted in the pipework to indicate water flow tempe...

Page 14: ...d to the earthing system and never reverse the Live and Neutral connections 9 2 GAS TRAIN INSTALLATION The gas train installation should be carried out by suitably qualified and competent personnel Be...

Page 15: ...made up by inserting the flue plates and locking nuts into position with nuts and bolts The plates MUST be inserted into the sections in the slots provided and the number and position of the plates MU...

Page 16: ...TISBURY 500001118 C Figure 10 2 Boiler Section Identification A Rear Intermediate section RI Fitted with 4 flue plates C Front Intermediate section FI Fitted with 2 flue plates B Intermediate section...

Page 17: ...aps through the ports or flueways IT IS MOST IMPORTANT THAT THE BACK EDGES OF THE FEET ON THE CASTING ARE FLUSH WITH THE REAR OF THE CRADLE TO ALLOW FOR CORRECT FITTING OF THE CASING b Fit sealing mas...

Page 18: ...Figure 10 6 Fitting O Ring Seal c Insert guide rings 6 into both upper and lower ports and fix in place using a small piece of the mastic sealing material Fig 10 5 d Carefully fit O ring gaskets 5 ove...

Page 19: ...of the UPPER RIGHT and LOWER LEFT pairs of bolt flanges on the sections Fig 10 7 Tighten the bolts EVENLY to a torque of 25Nm 18 lbf ft N B These bolts are intended only to keep the sections together...

Page 20: ...gure 10 9 Fitting Lower Tie Rods Figure 10 10 Flue Gas Flow Path h After fitting front section 2 fit the four tie rods 30 through the lugs on top and bottom of front and rear sections Figs 10 8 10 9 T...

Page 21: ...board large enough to accept the burner blast tube Note Burner mounting plate NOT required on SP 280 and SP 340 models c Locate the foil covered insulation wrap which comprises a front blanket a rear...

Page 22: ...uts and washers fit front and rear cross members to M6 studs protruding from body of boiler 2 Using M6 nuts and washers fit casing support rails to M6 studs on front and rear cross members Note positi...

Page 23: ...ion 5 Attach casing support strut to front edges of side panels and secure with M5 x 10 pozi screws and washers Note On assemblies with two side panels secure panels together with M8 x 16 hex head scr...

Page 24: ...ashers Note Ensure that rear cover is located in correct position as indicated below 8 After mounting burner on burner mounting plate fit plastic strikers and latches to upper and lower covers and sid...

Page 25: ...burner and the Live and Neutral should be correctly connected c The gas pipe work is of a suitable size for the burner requirements and the installation has been checked for leaks and fully purged On...

Page 26: ...y until the desired level is reached h Replace the gas valve security cover i Manually drive the fan speed back to maximum by pressing the hidden button at the same time as the plus button Once again...

Page 27: ...lating water 4 The pipework and valve arrangement is installed to Hamworthy Heating recommendations in such a way that water flow rates will be in accordance with Figure 3 1 5 The gas supply pipework...

Page 28: ...figures nominated in section 10 6 of this manual IF BURNER REPEATEDLY FAILS TO LIGHT A FULL INVESTIGATION TO FIND CAUSE SHOULD BE MADE h Check gas flow rate at meter Ensure that all other appliances...

Page 29: ...r FLOW NTC1 and RETURN NTC2 temperature sensors have been exchanged Boiler FLOW NTC1 and RETURN NTC2 temperature sensors are not equal in rest position Boiler FLOW NTC1 and RETURN NTC2 temperature sen...

Page 30: ...HAMWORTHY HEATING LTD 24 SPETISBURY 500001118 C Figure 12 2 Fault Finding Flowchart...

Page 31: ...is manual e Examine all gasket material and check for any signs of damage or degrading If necessary replace them but always use the correct type f Check all electrical connections and cables to ensure...

Page 32: ...n procedure In each case the operation of each replaced component must be checked by carrying out the appropriate part of the commissioning procedure See Section 11 0 COMMISSIONING TESTING NOTE Isolat...

Page 33: ...82 Not Required on SP 280 or SP 340 Models 13 Burner Mounting Plate 530805065 Not Required on SP 280 or SP 340 Models 14 Sight Glass Insulation Gasket 573405184 15 Sight Glass Assembly 573405185 16 Ga...

Page 34: ...er Head Gasket 533306069 Fan Gasket 533306070 Burner Head 533306071 Inlet Gas Flange kit 533306072 Gasket Kit 563605284 Service Kit 563605285 Fan Control Control Box Gas Valve Electrodes Burner Head B...

Page 35: ...it 533306076 Gasket Kit 563605284 Service Kit 563605285 Spetisbury SP 280 Control Box 533306079 Gas Valve 533306080 Fan Unit 533306081 Mounting Plate Gasket 533306082 Burner Head Gasket 533306083 Fan...

Page 36: ...HAMWORTHY HEATING LTD 30 SPETISBURY 500001118 C Figure 15 1 Boiler Installation Typical 15 0 TECHNICAL DATA...

Page 37: ...It may not however be adequate for the installation of flue bends within the boiler house Where necessary the dimension must be increased accordingly Figure 15 3 Burner Clearances Boiler Burner Model...

Page 38: ...HAMWORTHY HEATING LTD 32 SPETISBURY 500001118 C STACKED BOILER DIMENSIONS Front View Figure 15 4 Stacked Boiler Dimensions...

Page 39: ...ate is supplied the dimensions of which are shown below Figure 15 5 SP 110 150 220 Burner Mounting Plate Dimensions When installing a Spetisbury SP 280 or SP 340 a burner mounting plate is not require...

Page 40: ...t3 h 6144 8333 10381 13532 16501 GAS DATA NOMINAL GAS INLET PRESSURE mbar 20 MAXIMUM GAS INLET PRESSURE mbar 25 GAS FLOW RATE m3 h 13 3 18 2 26 5 32 8 39 9 ft3 h 469 5 642 5 935 5 1157 1410 GAS INLET...

Page 41: ...SP 150 206 7 45 4 6 5 2 6 108 23 8 1 8 0 7 SP 220 286 7 63 1 11 5 4 5 157 7 34 7 3 7 1 5 SP 280 357 5 78 6 16 5 6 6 196 3 43 2 5 0 2 0 SP 340 435 0 95 7 21 0 8 4 240 0 52 8 6 4 2 6 Figure 3 1 Water F...

Page 42: ...HAMWORTHY HEATING LTD 36 SPETISBURY 500001118 C NOTES...

Page 43: ...Notes...

Page 44: ...y reserves the right to make changes and improvements which may necessitate alteration to the specification without prior notice Connect direct Direct Dial Telephone and Fax Numbers Direct Email Addre...

Reviews: