Tyneham Heat Pump Control
-
Installation, Use and Maintenance
3.2.
Installation of flow sensor in the tank or decoupling bottle
figure 8 - Flow sensor on decoupling tank
The initial temperature sensor B10 must be located at
the top of the water tank as close as possible to where
the heating outlet connection. Refer to the drawings
for the heating system design to determine the precise
location.
Mount the specific Tyneham immersion sleeve
supplied with the tank or bottle in the opening located
in the upper section.
- on a bottle : 100mm immersion sleeve to be placed
in the upper opening at 90° from the flow opening.
- on a primary water tank: 160mm immersion sleeve
to be placed in the upper opening at 45° from the flow
opening.
Temperature sensor B10 is inserted all the way into
the immersion sleeve and held in place using the seal
provided.
B10 flow sensor opening
Immersion sleeve lg 160mm
To Tyneham
DHW station
!
CAUTION:
Use the specific Tyneham immersion sleeve supplied with the tank or
bottle.
B10 flow sensor opening
Immersion sleeve lg 100mm
Tyneham DHW
station
Tyneham
Heat pump
figure 9 - Flow sensor on decoupling bottle