HAMWORTHY HEATING LTD
50
UPTON FLOOR STANDING SERIES
500001340/C
Fault Alarm and Run Signal
Parameters are pre
-
programmed into Navistem Controller.
Extension module AGU2.550A109 is required for each boiler. Set the dip switch to 1. The parameters in the LMS
are set to acknowledge module No.1 as the VFC outputs
Note: A maximum of three extension modules can be accommodated per boiler. Using this option reduces the
number of addition heating circuits that can be controller by the boiler from three to two.
Connections on extension module AGU2.550A109.
Volt Free Connections
L (1) Low voltage supply (24v Signal)
QX21 (7)
-
Switch Closed
-
Run Signal
QX22 (5)
-
Switch Closed
-
Fault Signal
Mains Supply 230V Signal
L (1)
-
connected to AUX2 L
N (2)
-
connected to AUX2 N
QX21 (7)
-
Switch Live
-
Run Signal
N (4)
-
Neutral
-
Run Signal
QX22 (5)
-
Switch Live
-
Fault Signal
N (6)
-
Neutral
-
Fault Signal
Boiler Parameter Settings: Single Boiler
Enable with external time clock for constant temperature
Legend
E = End user
I = Commissioning
F = Heating engineer
Menu
Operating Line
User Level
Function
Setting
LPB System
6600
F
Device address
1
6630
F
Cascade Master
Automatically
Configuration
5710
F
Heating circuit 1
Off
5977
F
Function of input H5
Consumer request VK1
Consumer Circuit 1
1859
F
Flow temperature setpoint
80°c or as required
Note:
Use H5 wiring connection to enable boiler requires volt free enable from time clock.
Optional extras required for this configuration:
None
Using the boiler control to set the pump speed (pumps with 0
-
10v control).
Legend
E = End user
I = Commissioning
F = Heating engineer
Menu
Operating Line
User Level
Function
Setting
Boiler
2323
F
Pump speed maximum
% Set as required to achieve
20°C temperature differential
2322
F
Pump speed minimum
Same % value as 2323
Diagnostics Heat
8310
F
Display boiler flow temp.
Display only
Generation
8314
F
Display boiler return temp.
Display only
The pump is defaulted to pump speed min 100% & pump speed max 100% to adjust these values you will need to
do the following.
On the HMI press
OK,
time and date will appear.
•
Press and hold the
I
button for 3
-
5 seconds
Boiler Parameter Settings: Individual Boiler Shunt Pumps 0
-
10v