HAMWORTHY HEATING LTD
54
UPTON FLOOR STANDING SERIES
500001340/C
Menu
Operating Line
User Level
Function
Setting
Configuration
5710
F
Heating circuit 1
On
1—on/off
5950
F
Function of remote
Operating mode
Input H1
changeover HC1
5951
F
Define time clock
As required
Switch—no/nc
contacts
Heating mode
Auto symbol
Hot water mode
Off
Optional extras required for this configuration:
Heating sensor kit – QA236
Part number 563605673
LPB bus
communication module OCI345—one per boiler module
Part number 563605667
Individual boilers enabled from B.M.S. using 0
-
10V analogue input
Legend
E = End user
I = Commissioning
F = Heating engineer
Navistem settings
BMS 0
-
10v Power Control
Menu
Operating Line
User Level
Function
Setting
LPB System
6600
F
Device address
1
Configuration
5710
F
Heating circuit 1
Off
5950
F
Function input H1
Output req VK1 10v
5951
F
Contact type H1
NO
5953
F
Voltage value H1
0.1v
5954
F
Function value 1 H1
200 (200 = 20% modulation)
5955
F
Voltage value 2 H1
10.0v
5956
F
Function valve 2 H1
1000 (1000 = 100% modulation)
5890
F
Relay output QX1
Boiler pump Q1
BMS 0
-
10v Temperature
Menu
Operating Line
User Level
Function
Setting
LPB System
6600
F
Device address
1
Configuration
5710
F
Heating circuit 1
Off
5950
F
Function input H1
Consumer req VK1 10v
5951
F
Contact type H1
NO
5953
F
Voltage value H1
0.5v
5954
F
Function value 1 H1
0 (0 = 0°C)
5955
F
Voltage value 2 H1
10.0v
5956
F
Function valve 2 H1
800 (800 = 80°C)
5890
F
Relay output QX1
Boiler pump Q1
Note:
Use H1 wiring connection for 0
-
10V analog input from B.M.S.
Optional extras required for this configuration:
None
Boiler Parameter Settings: Multiple Boilers