8.0 INITIAL LIGHTING
Only competent persons registered for working on non
-
domestic gas appliances should attempt the following
operations. Before attempting to commission any boiler, ensure that personnel involved are aware of what action
is about to be taken.
8.1 Carry out the following procedure to fire up the boiler:
1. Ensure the boiler module gas service (isolating)
valve is closed
(Figure 8.1.1)
Figure 8.1.1
-
Gas Isolating Valve
2. Check and adjust if necessary the low gas inlet
pressure switch located on the side of the boiler gas
valve (fig. 8.1.2).
Setting should be
97, 116 &147 to 7 mbar
196 and 254 to 7.5 mbar
3. Switch on the electrical supply, and initiate the start
up sequence. Refer to
separate Navistem manual,
HHL part no. 500001310.
4. As the gas valve is closed, the low gas pressure
switch will prevent the boiler from firing and the error
code ‘E132’ will be displayed on the screen. Refer to
separate Navistem manual,
HHL part no.
500001310.
5. If the above procedure occurs correctly, open the
gas isolating valve and the fault indication will
extinguish.
The boiler will commence its ignition sequence as
previously described. This time, when the gas valve is
energised the burner will ignite.
6. With the burner firing, the flame signal displayed, should be approximately 9
-
12µA, but not less than 3µA. Refer
to
separate Navistem manual,
HHL part no. 500001310.
•
At the end of the ignition proving period, 5 seconds, the hot surface igniter system will be switched off.
•
After a period of 15 seconds the fan will alter speed and the burner modulation will be set according to the
heat load.
•
If after the 5 second flame proving period the flame signal is below 3µA the boiler will shut down and
attempt one restart.
NOTE: THE BOILER IS EQUIPPED WITH A RESTART FACILITY AND WILL ATTEMPT A SECOND IGNITION,
DURING WHICH THE ABOVE PROCEDURES WILL BE REPEATED. AT THE END OF THE RESTART
PROCEDURE, IF NO FLAME IS DETECTED AFTER THE FLAME PROVING PERIOD, THE BOILER WILL
LOCKOUT. THE BOILER WILL NOT OPERATE UNTIL THE LOCKOUT HAS BEEN MANUALLY RESET.
Figure 8.1.2
-
Low Gas Inlet Pressure Switches
196/254
97/116/147