HAMWORTHY HEATING LTD
54
Wessex ModuMax
mk3
Boilers
500001308/C
Enable with external time clock for constant temperature
Legend
E = End user
I = Commissioning
F = Heating engineer
Menu
Operating Line
User Level
Function
Setting
LPB System
6600
F
Device address
1
6630
F
Cascade Master
Automatically
Configuration
5710
F
Heating circuit 1
Off
5977
F
Function of input H5
Consumer circuit VK1
Consumer Circuit 1
1859
F
Flow temperature setpoint
80°c or as required
Note:
Use H5 wiring connection to enable boiler requires volt free enable from time clock.
Optional extras required for this configuration:
None
Boiler Parameter Settings: Single Boiler
External time clock with weather compensation
Legend
E = End user
I = Commissioning
F = Heating engineer
Menu
Operating Line
User Level
Function
Setting
LPB System
6600
F
Device address
1
6630
F
Cascade Master
Automatically
Heating Circuit 1
900
F
Operating mode Changeover
Automatic
Configuration
5710
F
Heating circuit 1
On
5977
F
Function of input H5
HCS
5978
F
Contact type H5
NC
Heating Circuit 1
740
F
Flow temp min set point
50
741
F
Flow temp max set point
80
720
F
Heating curve slope
3
726
F
Heating curve slope adaption
On
Operation section
26
F
Operation lock
On
Hot water mode
No display
Note:
Use H5 wiring connection to enable boiler requires volt free enable from time clock.
Optional extras required for this configuration:
External air sensor
– QAC34
Part number 533901457
Room sensor choice
– QAA55—Offset adjustable room sensor
Part number 533901589
– QAA75—Programmable room sensor
Part number 533901587