background image

 

User Manual RCx-B-xxxAx-8.09 

 

 

 

Page 2 of 18

                                                                                                                         

www.hanbayinc.com | 1 800 315 4461      

Rev.2021.8                                                                                                                                                                              hanbaysales@hanbayinc.com 

INSTALLATION 

 

 

Mounting 

 
The holes indicated in the image are intended for a mounting 
bracket. They are threaded for ¼-

20 and are 0.4” deep.   

 
The other two visible holes are threaded 10-

32, 0.50” deep, and are 

intended to be used to lock the lid in position with screws. 
 
 
For detailed dimensions see p.13. 

 

 

 

 

 
 
Wiring 

 

Wiring for Explosion Proof Actuators 

 

The 

RCx-AC-B-BxxAx

 Explosion-Proof actuator does 

not

 come with a pre-installed cable, nor 

cable gland. A cable gland that meets site specifications for the appropriate hazardous location 
rating is required for installation. The cable gland and the cable for hazardous location should 
be installed by qualified personnel in accordance with site and local requirements.  
 

 
The actuator comes standard with a ½” FNPT thread cable entry. See p.14 for 
location of ½” FNPT housing access. A cable with 6 wires is required; it is 
recommended to use 3x 16 AWG for wires supplying power and ground, and 3x 20 
AWG for wires used for the control and feedback signals. 
 
 
 

Standards for cable gland and cable in hazardous locations: 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

* In explosion-proof models, the FNPT thread is not intended for conduit connection. Cable gland only. 

 

Compliance Standards 

Required to be Met 

Cable Types Permitted in  

Class I Division 1 

Hazardous Locations 

ANSI / UL 514B, ANSI / UL 

1203, ANSI / UL 2225, C22.2 

Non-Armored Extra Hard 

Usage Cord & TC-ER-HL 

ANSI / UL 514B, ANSI / UL 

1203, ANSI / UL 2225 

Armored IEEE 45 & IEEE 

1580 Marine Shipboard Cable 

ANSI / UL 514B, ANSI / UL 

1203, ANSI / UL 2225 

MC-HI, ITC-HL 

ANSI / UL 514B, ANSI / UL 

1203, C22.2 

Teck 90 (Canada Only) 

Summary of Contents for RC Series

Page 1: ...Explosion Proof Actuators 2 Wiring for Non Explosion Proof actuators 4 Power Supply and Current Draw 4 Control Signal and Feedback 5 Operation 6 DIP switches 6 Controlling the Actuator 6 Changing the...

Page 2: ...ocation should be installed by qualified personnel in accordance with site and local requirements The actuator comes standard with a FNPT thread cable entry See p 14 for location of FNPT housing acces...

Page 3: ...d cable gland are installed connect the wires to the pins on the terminal block as indicated here Pin Function 6 Already Connected to battery board then transformer board serially Connect live wire to...

Page 4: ...moving the actuator draws approx 5 mA AC power is connected to the RED BLACK wires with crimp connectors WM18225 DN WM18230 ND 18 22 AWG Ground is connected on the panhead ground screw circled in yell...

Page 5: ...e actuator 4 20 mA output is internally supplying the signal current and can drive sufficient voltage for any sensing resistor of up to 250 ohms The potential of the external GND after the sensing res...

Page 6: ...IP 6 and 8 are on then the total turns of the actuator would be five 9 Signal loss See p 10 10 11 Seating Torque Set how much torque the actuator exerts on the valve lever during the calibration findi...

Page 7: ...0 0 1 0 0 0 1 2 0 0 1 0 3 0 0 1 1 4 0 1 0 0 5 0 1 0 1 6 0 1 1 0 7 0 1 1 1 8 1 0 0 0 9 1 0 0 1 10 1 0 1 0 11 1 0 1 1 12 1 1 0 0 13 1 1 0 1 14 1 1 1 0 15 1 1 1 1 WARNING Be sure that the number of turns...

Page 8: ...double the power set by DIP 10 and DIP 11 up to 100 power This pull out function is always enabled Speed and Torque Details The maximum speed of the actuator can be set by using the first two positio...

Page 9: ...de torque values by 3 To convert in lbs to Nm divide by 9 RCH AC B xxxAx Actuators Speed Torque DIP 1 DIP 2 Time for 1 turn sec DIP 10 DIP 11 Seating Torque in lbs Operating torque is 100 OFF OFF 90 O...

Page 10: ...ition The default signal position is an absolute actuator position i e not a signal value 3 Re zeroing the actuator and initiating calibration routine The actuator will re zero when the input signal i...

Page 11: ...anually If the valve is moved with the manual override when its power is turned off it will lose its position and it will need to be re zeroed as described in the Signal Loss and Calibration section T...

Page 12: ...onths without power being applied The fail safe actuation can be performed for 30 cycles on the charge available in the battery During normal operation from totally discharged the batteries will take...

Page 13: ...x AC B BxxAx IECEX Standards Editions IEC 60079 0 2017 7th Edition IEC 60079 1 2014 7th Edition Serial number will be engraved on the lid CSA Standards Class I Div 1 Groups B C D T6 Class II Groups E...

Page 14: ...User Manual RCx B xxxAx 8 09 Page 14 of 18 www hanbayinc com 1 800 315 4461 Rev 2021 8 hanbaysales hanbayinc com ACTUATOR DIMENSIONS RCJ RCL RCM AC B xxxAx models...

Page 15: ...User Manual RCx B xxxAx 8 09 Page 15 of 18 www hanbayinc com 1 800 315 4461 Rev 2021 8 hanbaysales hanbayinc com RCH AC B xxxAx models...

Page 16: ...User Manual RCx B xxxAx 8 09 Page 16 of 18 www hanbayinc com 1 800 315 4461 Rev 2021 8 hanbaysales hanbayinc com RCF AC B xxxAx models...

Page 17: ...User Manual RCx B xxxAx 8 09 Page 17 of 18 www hanbayinc com 1 800 315 4461 Rev 2021 8 hanbaysales hanbayinc com PART NUMBER BREAKDOWN Full Hanbay Part Number...

Page 18: ...Part Number Refer to part number breakdown for available options Ex proof Certification Info on ex proof ratings and installation instructions Actuator Serial Number This serial number is unique for...

Reviews: