current of the motor is locked rotor current.
Starting current: the maximum current reached before the motor input current reaches the stable state.
The highest start and stop frequency: 6 times per hour;
Shortest operation time: 5 minutes
2.5
Installation and fixation
When it is applied to normal system, the compressor must be installed horizontally.
It is suggested that the compressor should not be installed directly on the heat exchanger. If the compressor
must be installed in that way due to condition restriction, please ensure the strength of the load-bearing
structure.
It is suggested to use a fixed steel structure supporting frame to install the compressor and use the damping
pad to reduce the effect of compressor vibration on the system.
For marine system, the compressor should be installed along the axial direction of the ship, and the
external oil tank and pressure maintenance valve need to be configured. Please contact Hanbell for more
installation suggestions.
Figure-Installation diagram of compressor damping pad