LB
II
-PLUS Technical Manual
32
length
<1.8KΩ
30M
—
Switching frequency
—
Phase stagger
—
Phase loss
Cancel deadlock or reset
delay
5min±1min
Deadlock
Deadlock
Power off and reset
Ambient temperature
-30…70
℃
Max switching frequency
Switch for 3 times within
30s
Phase monitor
—
Phase sequence
—
Phase loss
—
Inactivation
Activated 1 second after the motor
starts and will remain monitoring for
5 seconds;
Activated 1 second after the motor
starts and will remain monitoring till
the machine stops;
About 20 seconds after the motor
stops.
Delay reset relay
—Power
—Mechanical lifetime
AC 240V 2.5A C300 at least
AC/DC 24V 20mA
One million times on and
off switching
D.
Signal light flashing
The signal light is for convenient, fast and easy maintenance; the signal is composed of red and orange. The
current state of light flashing depends on the number of pulse flashes.
Signal is as below:
Pause 1 time
RED
Pause twice
Orange
Pause 1 time
(Pause flash: 1-5times) (Pause flash: 1-5times)
Description
Green
Compressor operation
Green flash
Compressor operation
Red/ Organ flash
Faults occur; relay jump off; compressor stop; please refer
to below table
First flash sequence
(red light)
Second flash sequence
(organ light)
Description
1
1
Motor temperature: static jump off; winding
temperature over high
3
Motor temperature: reset delays after static
jump off
4
Motor temperature: temperature sensor detects
open circuit or short circuit
2
1
Motor voltage: phase sequence wrong
2
Motor voltage: phase stagger/three phase
asymmetry
3
1
Power supply voltage: module access power
supply too low