LB
II
-PLUS Technical Manual
33
If the green light is always on but the compressor cannot start: Use the multimeter to test the resistance
between M1 and M2. If it is blocked, the protector needs to be replaced.
E.
Appearance and wiring
Figure - INT69 HBY Diagnose diagram
Figure-INT69 HBY&PTC connection diagram
Note:
The above figure only indicates the connection method of protection module; it is not the compressor
startup mode.