-PLUS Technical Manual
21
Attention:
For parallel system, the liquid level switch should be installed on the external oil separator to avoid
affecting the compressor oil return due to the low oil level.
For parallel system, the external oil heater should be installed on the external oil separator. The oil heater
on-off is controlled by the oil temperature sensor inside the oil separator.
For parallel system, an oil filler and oil relief valve should be installed on the external oil separator to ease
the replacement and supplement of lubricant.
Cannot start the compressor, if temperature of the system lubricating oil is lower than 20
℃
or higher than
60
℃
.
For more information about the oil line, please contact HANBELL
2.4
Motor control
2.4.1
Part winding start
Hanbell screw compressor is equipped with part winding start (PWS) motor.
——A connect to PTC
——B connect to NTC
Figure- Compressor wiring
Figure
Part winding start
Figure
Compressor motor wiring
Z
U
W
X
Y
V