LT-S-(L) Technical manual
Max. working temperature
105
℃
Power 220V/ 50HZ
10.3.2
Oil Line Solenoid Valve
Oil Line Solenoid Valve
Oil circuit solenoid valve appearance
10.3.3
Oil Pressure Differential Switch
Function: Detect the pressure drop before and after the oil filter. If the pressure
drop exceeds the trip point, the switch will be activated to prevent the excessive
debris to be absorbed at the filter film, which will damage the oil supply system.
Specification: Hanbell standard trip valve is 1.5 bar and the valve can be reset
manually.
Instructions: For compound compressor without external oil line system, the high
pressure connector (HP) of the pressure differential switch is connected to the
high pressure connector of the compressor (high pressure angle valve or
discharge oil separator side angel valve) ; the low pressure connector (LP) is
connected to the oil filter flange of the compressor. When the oil resistance
exceeds the set valve (1.5 bar), the pressure differential switch (OFF) cuts off the
compressor control circuit to remind the user to clean the filter.
For compressors connected in parallel or compound compressor with external oil
line, the oil pressure differential switch shall be installed on the inlet and outlet of
the external oil filter. When the circuit is cut off, please clean or change the oil
filter.
Direction arrow at the bottom
“ ”