LT-S-(L) Technical manual
of pulsed flashes.
The signal is as follows
Pause 1 time red Pause 2 times orange Pause 1
time
(
1-5 times pulse
)
(
1-5 times pulse
)
Signal
light
overview
Green
Compressor operation
Flashing green
Compressor running
Flashing
red/orange
Fault, relay tripped, compressor down
;
See the table below
for details.
First blinking sequence
(
red
)
Second blinking
sequence
(
orange
)
description
1
1
Motor temperature: static trip, winding
temperature is too high
3
Motor temperature: reset delay after static
trip
4
Motor temperature: The temperature
sensing element detects an open or short
circuit
2
1
Motor voltage: phase sequence error
2
Motor voltage: wrong phase / three phase
asymmetry
3
1
Power supply voltage: module is too low
for power supply
The green light is on but the unit cannot be started: use the multimeter resistance file to measure
the conduction between M1 and M2. If the M1-M2 is not conducting, replace the protector.