LT-S-(L) Technical manual
3.2.2
Stepless type capacity modulation system
Stepless type is suitable when the refrigeration system needs to achieve precise
control of cooling capacity.
1
)
Stepless type control logic
N: Do not energize the solenoid valve
LT series
Capacity
modulation system
SV1: unload
(NC)
SV2:10%
(NC)
SV3:50%
(NC)
SV5:100%
(NC)
Load
N
N
N
Pulse activating
Unload
Pulse activating
N
Stay energized
N
Keep load state
N
N
N
N
10% load
(
start/shutdown
)
Stay energized
Stay energized
N
N
Table 3-2. Stepless Type Capacity Modulation Control Logic 50%~100%