LT-S-L Technical manual
Figure 5-4. Minimum Pressure Valve Installation Graph
Minimum Pressure Valve Configuration Compound & Parallel Connection
Model
Compound
Parallel connection
Two in parallel Three in parallel Four in parallel
LT-20/10
2”
3”
4”
5”
LT-45/20
2.5”
4”
5”
6”
LT-55/25
2.5”
4”
5”
6”
LT-65/32
2.5”
4”
5”
6”
LT-83/41
2.5”
4”
5”
6”
Fig 5-1.
Table 5-1. Minimum Pressure Valve Configuration Compound &
Parallel Connection
★
Note
:
For LT series compressors, the standard minimum pressure valve size we provide to you
is the same as that of the discharge valve.
★
Note
:
Besides the standard size, other sizes are optional (refer to 10.2.4)
★
Note
:
LT series compressor must be equipped with minimum pressure valve.
5.1.4
Liquid Line Filter Dryer
It will cause damage to the compressor and system even a low moisture content
left in the system, so it’s a must to install a filter drier on liquid line to keep the system
dry.
5.1.5
Sight Glass with Moisture Indicator
It is strongly recommended to install the sight glass with moisture indicator in
order to observe the moisture content in the system. When the moisture content is
high, it is necessary to change the filter dryer
★
Note
:
Hanbell can provide the sight glass with moisture indicator as an option.