LT-S-(L) Technical manual
liquid level switch is lower than the control oil level line for a period of time (5±2 s),
the liquid level switch sends a signal to supply oil to the compressor.
;
When the oil
level is higher than the control oil level line for a period of time (5±2s), the liquid
level switch is automatically reset.
If the oil level detected by the optical level switch is lower than the control oil
level line for a period of time, the liquid level switch sends a signal, and the
compressor oil level does not reach the control oil level line during the period of
60-90 s. , the compressor will cut off the motor power line for a protective shutdown.
Fault analysis and processing
symptom
problem analysis
Solution
Liquid level alarm
in correct level
1.
The mirror detection head is
covered with dirt
;
2.
The surface of the mirror is
scratched and opaque
1.
Cleaning the dirt attached to the mirror
;
2.
Replace the new mirror.
The semaphore is
displayed
as
"abnormal"
1.220V Low voltage
;
2.The
temperature
of
the
medium is too high, causing
damage
to
the
internal
components of the module.
;
3
Module and connector are not
tightened
;
4.
Coil damage
1.
Connect the LN terminal power supply, the
voltage value should be within the specified
range
;
2.
The temperature at which the photo-liquid
switch operates is within its allowable range
;
3.
Lock the joint nut with your bare hands
;
4.
Replace the coil
Action
delay
invalid or error
1.
Wiring error
;
2.
Coil damage
1.
Wiring according to the correct wiring
;
2.
Replace the coil
Note ,that the optical level switch is not working properly and there are the following possibilities::
1. Use environmental chemicals to damage the liquid liquid coil wire, etc.
;
2. The humid environment causes a short circuit in the photo-liquid coil.
10.5
Other accessories
10.5.1
Cushion
To avoid additional vibration and noise due to direct contact between the
compressor and its mounting feet and mounting base, it is recommended to install
a cushion under the compressor foot. The torque required for the installation of the
damping pad is 20~30N.m.
Note
:
The position of the compressor
anchor
is detailed in 7.3
size and specification sheet
:
fig10-12.
compressor
cushion
specification sheet
: